Making the hydraulic connections
1. Equip the primary circuit with an expansion vessel
and safety valve (to DIN 4757).
Note
The expansion vessel must be approved to
DIN 4807. The diaphragms of the expansion ves-
sel and safety valve must be suitable for the heat
transfer medium.
The blow down and drain pipes should terminate
in a container. This container must be able to
hold the maximum possible expansion volume of
the heat transfer medium.
2. Provide thermal insulation and anti-vibration meas-
ures for all line entries.
3. Connect the primary lines to the heat pump.
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibrations and appliance dam-
age.
Connect on-site lines so that they are free of
load and torque stress.
!
Please note
Leaking hydraulic connections lead to appli-
ance damage.
Ensure the diaphragm grommets at the hose
outlets are seated correctly. Seal hose out-
lets with sealing tape if necessary.

Connecting the secondary circuit

1. Equip the secondary circuit on site with an expan-
sion vessel and safety assembly (to DIN 4757).
Fit the safety assembly to the on-site line in the
heating water return.
2. Connect the secondary lines to the heat pump
(
28 mm).
7 ≥
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibrations and appliance dam-
age.
Connect on-site secondary lines to the heat
pump so they are free of load and torque
stresses.
!
Please note
Leaking hydraulic connections lead to appli-
ance damage.
Ensure the diaphragm grommets at the hose
outlets are seated correctly. Seal hose out-
lets with sealing tape if necessary.
12
(cont.)
4. Apply thermal and vapour diffusion-proof insulation
to all lines.
5. Fill the primary circuit with Viessmann heat transfer
medium and vent.
Note
Ensure frost protection down to
Viessmann heat transfer medium is a ready-mixed
ethylene glycol-based medium. It contains inhibi-
tors for corrosion protection. The heat transfer
medium can be used at temperatures down to
19 °C.
6. Check the diaphragm grommets: See page 28.
3. Fill and vent secondary circuit.
4. Thermally insulate all lines.
5. Check the diaphragm grommets: See page 28.
Note
Ensure the minimum flow rate, e.g. by means of an
overflow valve: See "Specification" on page 31.
19 °C.