Connecting The Secondary Circuit - Viessmann Vitocal 350-G Installation And Service Instructions Manual

Heat pumps with electric drive, 1 and 2-stage
Table of Contents

Advertisement

Installation sequence
Hydraulic connections

Connecting the secondary circuit

1. Equip the secondary circuit on site
with an expansion vessel and safety
assembly (in accordance with
DIN 4757).
Fit the safety assembly to the on-site
line in the heating water return.
2. Connect secondary lines to heat
pump (7 ≥ 28 mm).
!
Please note
To prevent equipment dam-
age,
connect on-site secondary
lines to the heat pump so that
they are free of load and tor-
que stresses.
!
Please note
Make tight hydraulic connec-
tions on the secondary side.
In the case of hose outlets,
ensure diaphragm grommets
are seated correctly. If neces-
sary, seal with sealing tape.
70
(cont.)
3. Fill and vent secondary circuit.
4. Thermally insulate pipes inside the
building.
Note
■ For diaphragm grommets, see
page 108.
■ In underfloor heating circuits, install a
temperature limiter on site to restrict
the maximum temperature of under-
floor heating systems.
■ Ensure the minimum flow rate, e.g.
with an overflow valve (see chapter
"Specification").

Advertisement

Table of Contents
loading

This manual is also suitable for:

745260974526107452611

Table of Contents