3.7.1.10 SWING 2
This value is similar to the Swing 1, but it controls the
temperature variation the system allows above and below
Swing 1's lower limit before calling for a second stage.
Once a second stage is activated, it will remain on until
the temperature set point has been reached. If a third
stage of heat is present in heat pump mode, Swing 2 is
used to control it from the stage 2 lower limit.
3.7.1.11 HEAT FAN CONTROL
Fossil fuel furnaces normally control the system fan while
the furnace is operating. Electric systems normally
require the thermostat to activate the fan. This setting
instructs the thermostat how to handle fan control during
heating. Electric heat and heat pumps generally require
the thermostat to activate the fan and therefore use the
electric setting.
3.7.1.12 HEAT FAN ON DELAY
This setting allows the installer to program the length of
time between heating activation and fan activation (delay
on make).
3.7.1.13 HEAT FAN OFF DELAY
This setting allows the installer to program the length of
time between heating deactivation and fan deactivation
(delay on break).
3.7.1.14 COOL FAN ON DELAY
This setting allows the installer to program the length of
time between cooling activation and fan activation (delay
on make).
3.7.1.15 COOL FAN OFF DELAY
This setting allows the installer to program the length of
time between cooling deactivation and fan deactivation
(delay on break).
3.7.1.16 FUTURE OUTDOOR SENSOR
This setting enables and disables an outdoor sensor if it
is present. The setting will be held NA if a sensor is not
present, and will be reset to NA If the sensor is discon-
nected for any reason, including removal of the thermo-
stat from its base-plate, the thermostat will automatically
disable the sensor changing the setting in this menu
from ON to NA. With an outdoor sensor present and
enabled, the outdoor temperature will be displayed alter-
nately with time. The word OUT will be visible to the right
of the temperature while the outside temperature is dis-
played.
3.7.1.17 INTERNAL TEMPERATURE SENSOR
This setting enables and disables the thermostats internal
temperature sensor. It may only be disabled if there are
indoor remote sensors present and enabled.
3.7.1.18 FUTURE INDOOR REMOTE SENSOR 1, 2, 3
Used to enable and disable the respective remote sensors
in a system. When more than one indoor sensor is used,
the values of their measurements are averaged for use in
temperature control.
3.7.2 INSTALLER SETUP MENU WITH FURNACE SYS-
TEM TYPE SELECTED:
Menu
Item
Di s pl a y
01
System Type
02
Heat Stages
03
Compressor Stages
04
Modes
05
Mi n i m um Run Ti m e
06
Deadband
07
Swi n g 1
08
Swi n g 2
09
Heat Fan Control
10
Heat Fan On Del a y
11
Heat Fan Off Del a y
12
Cool Fan On Del a y
13
Cool Fan Off Del a y
14
Outdoor Sensor (future)
15
Internal Temp Sensor
(future)
16
Remote Sensor 1
(future)
17
Remote Sensor 2
(future)
18
Remote Sensor 3
(future)
3.7.3 INSTALLER SETUP MENU WITH HEAT PUMP
SYSTEM TYPE SELECTED AND OUTDOOR FUTURE
SENSOR ENABLED:
Menu
Item Di s pl a y
01
System Type
02
Heat Stages
03
Compressor Stages
04
Modes
05
Mi n i m um Run Ti m e
06*
Heat Pump Lockout
07*
Heat Pump
Lockout Temperature
08
Deadband
09
Swi n g 1
10
Swi n g 2
11
Heat Fan Control
12
Heat Fan On Del a y
13
Heat Fan Off Del a y
14
Cool Fan On Del a y
15
Cool Fan Off Del a y
10
Sel e cti o ns
Furnace / Heat Pump
0 – 2
0 – 2
Heat-Off
Cool - Off
Heat-Off-Cool
Heat-Off-Cool - Auto
1 to 5 mi n
3°F(1°C) to 5°F(3°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
Gas / El e ctri c
0, 15, 30...180 sec
0, 15, 30...180 sec
0, 15, 30...180 sec
0, 15, 30...180 sec
NA/ON/OFF
ON/OFF
NA/ON/OFF
NA/ON/OFF
NA/ON/OFF
Sel e cti o ns
Furnace / Heat Pump
0 – 1
0 – 2
Heat-Off
Cool - Off
Heat-Off-Cool
Heat-Off-Cool -
Em Heat-Auto
1 to 5 mi n
ON, OFF
0°F- 50°F(-17°C-10°C)
3°F(1°C) to 5°F(3°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
El e ctri c
0, 15, 30...180 sec
0, 15, 30...180 sec
0, 15, 30...180 sec
0, 15, 30...180 sec
Defaul t
Furnace
2
2
*
*
*
*Heat-Off-
Cool - Auto
4 mi n
3°F(1°C)
0.25°F(0.15°C)
0.5°F(0.3°C)
Gas
0 sec
0 sec
0 sec
0 sec
NA/OFF
ON
NA/OFF
NA/OFF
NA/OFF
Defaul t
Furnace
1
1
*
*
*
*Heat-Off-Cool -
Em Heat-Auto
4 mi n
Off
0°F(-17°C)
3°F(1°C)
0.25°F(0.15°C)
0.5°F(0.3°C)
El e ctri c
0 sec
0 sec
0 sec
0 sec