17. Technical Data
Technical data provided are based on the air conditioner running under free frequency.
17.1 Cool Mode Performance Data
Unit setting: Standard piping length, Hi Fan, Cool mode at 60.8°F
Voltage: 208-230V
Outdoor
Combination
Air Temp.
(Capacity) (kW)
°C (°F) DB
22 (71.6)
25 (77)
29 (84.2)
32 (89.6)
1.6 + 1.6
35 (95)
40 (104)
43 (109.4)
46 (114.8)
22 (71.6)
25 (77)
29 (84.2)
32 (89.6)
1.6 + 2.0
35 (95)
40 (104)
43 (109.4)
46 (114.8)
22 (71.6)
25 (77)
29 (84.2)
32 (89.6)
1.6 + 2.5
35 (95)
40 (104)
43 (109.4)
46 (114.8)
22 (71.6)
25 (77)
29 (84.2)
32 (89.6)
1.6 + 3.2
35 (95)
40 (104)
43 (109.4)
46 (114.8)
22 (71.6)
25 (77)
29 (84.2)
32 (89.6)
2.0 + 2.0
35 (95)
40 (104)
43 (109.4)
46 (114.8)
16 (60.8)
17.5 (63.5)
TC
IP
TC
IP
3.97
0.62
4.09
0.61
3.93
0.71
4.06
0.71
3.83
0.81
3.98
0.82
3.73
0.88
3.88
0.89
3.60
0.94
3.75
0.95
3.33
1.02
3.45
1.03
3.13
1.06
3.23
1.06
2.90
1.10
2.98
1.08
4.45
0.72
4.59
0.71
4.40
0.82
4.56
0.82
4.30
0.94
4.46
0.95
4.18
1.02
4.35
1.03
4.04
1.09
4.20
1.10
3.73
1.18
3.87
1.19
3.50
1.23
3.62
1.23
3.25
1.27
3.34
1.25
5.07
0.89
5.23
0.87
5.02
1.01
5.19
1.01
4.90
1.16
5.08
1.17
4.76
1.25
4.95
1.27
4.60
1.34
4.78
1.35
4.25
1.46
4.41
1.47
4.00
1.52
4.13
1.51
3.71
1.56
3.81
1.55
5.92
1.09
6.10
1.07
5.86
1.24
6.06
1.24
5.71
1.42
5.93
1.43
5.56
1.54
5.78
1.56
5.37
1.64
5.58
1.66
4.96
1.79
5.15
1.80
4.66
1.86
4.82
1.86
4.33
1.92
4.45
1.89
4.92
0.85
5.07
0.84
4.87
0.97
5.04
0.97
4.75
1.11
4.93
1.12
4.62
1.20
4.81
1.21
4.46
1.28
4.64
1.30
4.12
1.40
4.28
1.40
3.87
1.45
4.01
1.45
3.60
1.50
3.70
1.48
36
Indoor Air Temp. °C (°F) WB
18 (64.4)
19 (66.2)
TC
IP
TC
IP
4.13
0.61
4.21
0.60
4.11
0.71
4.20
0.71
4.03
0.82
4.13
0.83
3.93
0.89
4.03
0.90
3.79
0.95
3.89
0.96
3.49
1.03
3.58
1.03
3.27
1.06
3.34
1.06
3.01
1.08
3.07
1.07
4.63
0.70
4.72
0.70
4.61
0.82
4.71
0.82
4.52
0.95
4.62
0.95
4.40
1.03
4.51
1.04
4.25
1.10
4.36
1.11
3.92
1.19
4.01
1.19
3.67
1.22
3.75
1.22
3.38
1.25
3.44
1.24
5.28
0.87
5.38
0.86
5.25
1.01
5.37
1.01
5.15
1.17
5.27
1.18
5.02
1.27
5.14
1.28
4.85
1.36
4.97
1.37
4.46
1.47
4.57
1.47
4.18
1.51
4.27
1.51
3.85
1.54
3.92
1.53
6.16
1.07
6.28
1.05
6.13
1.24
6.26
1.24
6.01
1.44
6.15
1.44
5.86
1.56
6.00
1.57
5.66
1.67
5.80
1.68
5.21
1.80
5.34
1.81
4.88
1.85
4.98
1.85
4.49
1.89
4.57
1.87
5.12
0.83
5.22
0.82
5.09
0.96
5.20
0.96
4.99
1.12
5.11
1.13
4.87
1.22
4.99
1.23
4.70
1.30
4.82
1.31
4.33
1.40
4.43
1.41
4.05
1.45
4.14
1.44
3.73
1.47
3.80
1.46
22 (71.6)
24 (75.2)
TC
IP
TC
IP
4.64
0.60
4.92
0.59
4.63
0.71
4.92
0.72
4.55
0.84
4.84
0.85
4.44
0.91
4.72
0.92
4.28
0.97
4.54
0.97
3.92
1.02
4.14
1.01
3.63
1.03
3.83
1.01
3.31
1.02
3.47
0.98
5.20
0.69
5.51
0.68
5.19
0.82
5.51
0.83
5.10
0.97
5.42
0.98
4.98
1.06
5.29
1.07
4.80
1.12
5.09
1.13
4.39
1.18
4.64
1.17
4.07
1.19
4.29
1.16
3.71
1.17
3.89
1.13
5.92
0.85
6.28
0.84
5.92
1.02
6.28
1.02
5.82
1.20
6.18
1.21
5.67
1.30
6.02
1.32
5.47
1.38
5.80
1.39
5.00
1.46
5.29
1.45
4.64
1.47
4.89
1.44
4.23
1.45
4.43
1.40
6.91
1.04
7.33
1.03
6.90
1.25
7.33
1.25
6.79
1.47
7.21
1.48
6.62
1.60
7.03
1.61
6.38
1.69
6.77
1.70
5.84
1.79
6.17
1.77
5.42
1.80
5.71
1.76
4.93
1.78
5.17
1.71
5.74
0.81
6.09
0.81
5.74
0.97
6.09
0.98
5.64
1.15
5.99
1.16
5.50
1.25
5.84
1.26
5.31
1.32
5.63
1.33
4.85
1.39
5.13
1.38
4.50
1.40
4.75
1.37
4.10
1.39
4.30
1.34