11. Operation Control

11.1 Cooling Operation

11.1.1
Outdoor fan control
When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted
according to figure below:
11.1.2
Annual Cooling control
This control is to enable cooling operation when outdoor ambient temperature is low.
Control start conditions:
Cooling operation is activated with compressor ON.
o
Outdoor ambient temperature is less than 59°F
o
Control contents:
When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will
o
operate according to figure below:
To improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for
2 minutes will be activated every 35 minutes under designated fan speed.
Control stop conditions:
When either one of the start conditions are not complied.
o
RPM free
59°F
RPM controlled
8.6°F
Stopped
OD temp.
RPM up
93.2°F
RPM unchanged
75.2°F
RPM down
66.2°F
Stopped
OD Pipe temp.
21
55.4°F
91.4°F
73.4°F
64.4°F