Assign Inputs Menu - Weil-McLain SlimFit 3 Series Advanced Manual

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SlimFit 3 Series:
Table of Contents

Advertisement

®
SlimFit
Series 3

ASSIGN INPUTS menu

Boiler Model, Altitude are critical settings.
Failure to set correctly could result in severe per-
sonal injury, death or substantial property damage.
Figure 33 SlimFit
Assign Inputs menu
– 56 –
&
&
(see Figure 25, page 46 to access CONTRACTOR menu)
Advanced Manual
:
%
1. Access contractor menus by pressing and holding the UP and
DOWN arrow keys at the same time for 7 seconds.
2. See Figure  25,  page  46 for the screen sequences up to the
CONTRACTOR menu.
MENU
PURPOSE
ITEM
• There are three inputs/outputs available on
each boiler. This menu allows assignment
Overview
of which inputs/outputs operate which
priority/system.
• See "SlimFit control Priorities & Input/
Outputs" on page 4 for an explanation of
priorities, inputs and outputs.
• Priority settings are adjustable. See page 52
through page 55 for priority options.
• The Assign Inputs menu is for designating
priorities to the correct inputs according to
the system installed.
INPUT 1
• Multiple inputs can use the same priority.
INPUT 2
• The Source line designates Input 1 as either
INPUT 3
thermostat controlled or 0–10V controlled.
(On Master/Shadow systems, this line is
not present and Input 1 is predetermined
as a thermostat-controlled input.)
• When choosing 0–10V as the Source, a
NOTICE screen will pop up explaining
the use of the 0–10V input. Press SAVE to
use this option, or press cancel to return
the input to TT1.
• The AUX PUMP/OUTPUT function en-
ables an output to turn on in a variety of
selectable conditions.
• See page 57 for explanations and recom-
AUX
mended applications.
PUMP/
OUTPUT
• In network boiler applications, outputs
assigned AUX PUMP/OUTPUT are con-
trolled by the master boiler, based on the
input/output and blower behaviors of all
boilers on the network.
Screens shown here are typical only.
Actual screens depend on control settings
chosen.
Part number 550-100-569/0321