COMMERCIAL CONDENSING GAS

ASSIGN INPUTS menu, BASIC mode

Boiler Model, Altitude and Fuel Type are criti-
cal settings.
severe personal injury, death or substantial property
damage.
TM
Figure 59 SVF
BASIC mode ASSIGN INPUT options (USER MODE must be set to BASIC) — see Figure 60, page 72
and Figure 61, page 72 for explanation of AUX PUMP/OUTPUT settings
Screens shown above are typical
only. Actual screens depend on
control settings chosen.
Part number 550-100-200/1018
Failure to set correctly could result in
MENU ITEM
Overview
INPUT 1
INPUT 2
INPUT 3
-
— Boiler Manual
FIRED WATER BOILER
1. Access contractor menus by pressing and holding the UP and
DOWN arrow keys at the same time for 7 seconds.
2. See Figure 56, page 68 for the screen sequences up to the CON-
TRACTOR menu.
DESCRIPTION
• There are three priority levels defined by the settings
chosen in Figure 58, page 70.
• For DHW priority, make sure PRIORITY 1 is defined
for a DHW system.
• If DHW priority is required and analog input is used
for space heating, assign INPUT 2 to the DHW aqua-
stat (TT2) and INPUT 1 as PRIORITY 2 and SOURCE
set to 0-10V.
• Assign priority (system type) for INPUT 1 — options are:
• PRIORITY 1 — assigns INPUT 1 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 1 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 1 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF
• NOTE: For INPUT 1 only, select SOURCE = TT1 for
thermostat input or 0-10V if analog input is required.
• Assign priority (system type) for INPUT 2 — options are:
• PRIORITY 1 — assigns INPUT 2 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 2 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 2 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF
• Assign priority (system type) for INPUT 3 — options are:
• PRIORITY 1 — assigns INPUT 3 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 3 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 3 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF
71