Fast-Track Setup - Steps - Weil-McLain SlimFit 3 Series Advanced Manual

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SlimFit 3 Series:
Table of Contents

Advertisement

®
SlimFit
Series 3
Fast-Track Setup — Steps
The
WIZARD
are made. In addition, all instructions in the
in severe personal injury, death or substantial property damage.
• Install boiler(s) per SlimFit boiler manual and all
applicable codes, including vent/air piping and water
Step 1
piping.
• See suggested piping in this manual and boiler manual.
Mechanical
Each boiler must be connected with primary/secondary
piping and supplied with a boiler circulator.
For details, see FIELD WIRING information beginning
on page 22.
BOILER POWER SUPPLY
• Connect minimum 120 VAC power to boiler as directed
on the boiler wiring diagram (on boiler and on page 32).
INPUTS & OUTPUTS
• Each boiler provides three input/output pairs. Input
circuits are 24 VAC. DO NOT apply voltage. Use dry
contacts only. Outputs are 120 VAC, 2.2-amps max (use
relays if loads exceed 2.2 amps or if outputs must be 24
VAC or must be isolated contacts).
Step 2
• The input/outputs can be used with zone thermostats and
Electrical
zone circulators or zone valves (requires isolation relays
unless valves are 120 VAC), providing up to three zones
per boiler on a multiple system.
• Each boiler also provides an unpowered output for its
boiler circulator. Use a external relay if circulator requires
more than 10.0 amps at 120 VAC.
• If a system pump is to be operated by the SlimFit
controls, connect the pump to any of the available
outputs. The system pump can be activated by a
remote contact or can be automatically activated on
heat demand. Set up for pump operation is done in the
ACTIVATE OUTPUT screen of the WIZARD.
Step 3
• Turn OFF the manual gas cock at the boiler to prevent
POWER ON
JDV ÀRZ GXULQJ VHWXS
• Select the START WIZARD option from the
initial screen BOILER SETTINGS menu (see
Figure 20, page 40).
Step 4
• Use on-screen help as needed. For additional
WIZARD
information, see details in this manual.
• DO NOT select SKIP WIZARD unless the control
LV WR EH FRQ¿JXUHG PDQXDOO\
• Some additional control settings may need to be
changed, depending on the application.
Step 5
• See explanation of SlimFit control operation and settings,
Finish setup
beginning on page 41.
• Apply the SlimFit boiler manual instructions to verify the
Step 6
installation and to start up the boiler, using combustion
Start-up
test instruments as directed.
– 10 –
&
&
must be used when using the
Fast-Track Setup
SlimFit
Follow all instructions in the
manual, including all pre-start-up inspec-
tions and final checks.
:
%
procedure. This is necessary to ensure that all required settings
boiler manual must be followed completely. Failure to comply could result
• As shown in the suggested piping examples, DHW tanks
can be either piped directly off of individual boilers or as a
separate zone in the heating system.
• See page 6 for additional information on multiple boiler
installation options.
SENSORS
• Connect an outdoor sensor, system supply sensor and
system return sensor to at least one of the boilers in a
multiple boiler system..
• Preferably, connect outdoor, system supply and system
return sensors to more than one boiler to provide
redundancy. If one of the sensors fails, the master boiler
SlimFit control automatically looks for an available sensor.
MULTIPLE BOILER COMM CABLES
• For multiple boilers, connect boiler-to-boiler communication
cables as directed on page 31.
ADDITIONAL INFORMATION
• )RU ÀRZ VZLWFK RU &$' LQWHUORFN ZLULQJ VHH page 31.
• For external limit connections, see page 27.
• For 0–10VDC inputs, see page 29.
ZONING METHODS
• See wiring and control setup information for typical zoning
applications beginning on page 36.
• See example systems beginning on page 14.
SlimFit
• Turn the boiler ON/OFF switch to ON.
boiler
• Follow the prompts on the screen to reach the BOILER
SETTINGS initial start-up screen.
• See Figure 20, page 40 for navigation information. Note
that the screen sequence changes after initial setup, as
shown.
• For high-demand loads requiring fast
response, such as network DHW, access the
NETWORK PRIORITY screen for the assigned priority
(see Figure 31, page 52). Change the MIN BOILERS to
the number of boilers needed for peak load.
Advanced Manual
SINGLE BOILERS — Set up the con-
trol following instructions in the
boiler manual. If ADVANCED settings
are required, change to A D VA N C E D
mode from the CONTRACTOR menu.
See ADVANCED mode setup information
elsewhere in this manual.
Part number 550-100-569/0321