To Determine The Complete Recharge Amount; Charging Refrigerant: Setup; To Charge Additional Refrigerant; To Activate/Deactivate The Vacuum Mode Field Setting - Daikin RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B Installer's Reference Manual

Hide thumbs Also See for RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B:
Table of Contents

Advertisement

INFORMATION
Piping length is the largest one way length of liquid piping.
To determine the additional refrigerant amount (R in kg) (in
case of pair)
L1:
R:
To determine the additional refrigerant amount (R in kg) (in
case of twin, triple and double twin)
1 Determine R1 and R2.
If
G1>30 m
G1≤30 m
(and G1+G2>30 m)
Length (total length of liquid piping−30 m)
0~10 m
10~20 m
R1:
0.35 kg
0.7 kg
R2:
0.2 kg
0.4 kg
(a)
Only for RZASG100~140.
(b)
Only for RZASG100+125.
2 Determine the additional refrigerant amount: R=R1+R2.
Examples
Layout
Additional refrigerant amount (R)
L2=7 m
Case: Twin, standard liquid pipe size
(Ø6.4 mm)
1 G1 Total Ø9.5 => G1=35 m
L3=5 m
(Ø6.4 mm)
G2 Total Ø6.4 => G2=7+5=12 m
2 Case: G1>30 m
L1=35 m (Ø9.5 mm)
R1 Length=G1−30 m=5 m
RZASG100
R2 Length=G2=12 m
3 R
L2=15 m
Case: Triple, standard liquid pipe size
(Ø6.4 mm)
1 G1 Total Ø9.5 => G1=5 m
L3=12 m
(Ø6.4 mm)
G2 Total Ø6.4 => G2=15+12+17=44 m
L4=17 m
2 Case: G1≤30 m (and G1+G2>30 m)
(Ø6.4 mm)
R1 R1=0.0 kg
L1=5 m (Ø9.5 mm)
R2 Length=G1+G2−30 m =
RZASG125
3 R
6.6.6
To determine the complete recharge
amount
To determine the complete recharge amount (kg)
Model
5~30 m
RZASG71
2.45 kg
RZASG100-125
2.6 kg
RZASG140
2.9 kg
(a)
Length=L1 (pair); L1+L2 (twin, triple); L1+L2+L4 (double
twin)
RZASG71~140M_V1+Y1
Sky Air Advance-series
4P486047-1 – 2017.04
L1 (m)
30~40 m
40~50 m
0.35 kg
0.7 kg
Then
Use the table below to determine
R1
R1=0.0 kg.
Use the table below to determine
R2.
20~30 m
30~40 m
40~45 m
(a)
(a)
1.05 kg
1.4 kg
(a)
0.6 kg
0.8 kg
1 kg
=> R1=0.35 kg
=> R2=0.4 kg
R=R1+R2=0.35+0.4=0.75 kg
5+44−30=19 m
=> R2=0.4 kg
R=R1+R2=0.0+0.4=0.4 kg
(a)
Length
30~40 m
40~50 m
2.8 kg
3.15 kg
2.95 kg
3.3 kg
3.25 kg
3.6 kg
6.6.7

Charging refrigerant: Setup

See
"6.5.3 Checking refrigerant piping: Setup" on
6.6.8

To charge additional refrigerant

WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, always use protective
gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the
gas stop valve and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
(b)
If pump down is needed in case of dismantling or relocating the
system, see
"11.3 To pump down" on page 26
6.6.9
To activate/deactivate the vacuum mode
field setting
Description
To perform vacuum drying or a complete recharge of the outdoor
unit's internal refrigerant piping it is necessary to activate the
vacuum mode which will open required valves in the refrigerant
circuit so the vacuuming process or recharge of refrigerant can be
done properly.
To activate vacuum mode:
Activating the vacuum mode is done by operating the push buttons
BS* on the PCB (A1P) and reading the feedback from the 7‑segment
displays.
Operate the switches and push buttons with an insulated stick (such
as a closed ball-point pen) to avoid touching of live parts.
1 When the unit is powered on and not running, hold down the
BS1 pushbutton for 5 seconds.
Result: You will reach the setting mode, the 7 segment display
will show '2 0 0'.
2 Press the BS2 button until you reach page 2–28.
3 When 2–28 is reached, press the BS3 button once.
4 Change the setting to '1' by pressing the BS2 button once .
5 Push the BS3 button once
6 When the display is not blinking anymore, press the BS3 button
again to activate vacuum mode.
To deactivate vacuum mode:
After charging or vacuuming the unit, please deactivate the vacuum
mode by changing the setting back to '0'.
Make sure to reattach the electronic component box cover and to
install the front cover after the job is finished.
6 Installation
page 16.
for more details.
Installer reference guide
19