Use Of Furnace As Construction Heater - Lennox SIGNATURE SLP99DFV Installation Instructions Manual

Table of Contents

Advertisement

Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cool-
ing units to avoid condensation in the heating compart-
ment. With a parallel flow arrangement, a damper (or
other means to control the flow of air) must adequately
prevent chilled air from entering the furnace (FIGURE 3).
If the damper is manually operated, it must be equipped to
prevent operation of either the heating or the cooling unit,
unless it is in the full HEAT or COOL setting.
FURNACE INSTALLED PARALLEL
WITH COOLING COIL
GAS UNIT
Dampers
(open during heating
operation only)
FIGURE 3
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum contin-
uous return air temperature of 60°F (16°C) or an inter-
mittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air tem-
perature must not exceed 85°F (29°C) dry bulb. See "Duct
System" on page 9 for installing the optional discharge
air sensor used to measure temperature rise. Sensor is
shipped with the unit.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
CAUTION
Do not set thermostat below 60F (16C) in heating mode.
Setting below 60F (16C) reduces the number of heating
cycles. Damage to the unit may occur that is not covered
by the warranty.
AIR HANDLER
Dampers
(open during cooling
operation only)
Page 5
The SLP99DFV furnace may be installed in alcoves, clos-
ets, attics, basements, garages, and utility rooms.
This furnace is not designed for installation in mobile
homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.

Use of Furnace as Construction Heater

Units may be used for heating of buildings or structures
under construction, if the following conditions are met to
ensure proper operation:
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT
UNLESS ALL OF THE FOLLOWING CRITERIA ARE
MET:
• Furnace must be in its final location. The vent system
must be permanently installed per these installation in-
structions.
• Furnace must be installed as a two pipe system and
one hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion.
• A room thermostat must control the furnace. The use
of fixed jumpers that will provide continuous heating is
prohibited.
• The input rate and temperature rise must be set per the
furnace rating plate.
• Supply and Return air ducts must be provided and
sealed to the furnace. Return air must be terminated
outside of the space where furnace is installed.
• Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
• MERV 11 or greater air filters must be installed in the
system and must be regularly inspected and maintained
(e.g., regular static checks and replaced at end of life)
during construction.
• Blower and vestibule access panels must be in place on
the furnace at all times.
• The furnace heat exchanger, components, duct system,
and evaporator coils must be thoroughly cleaned follow-
ing final construction clean−up.
• Air filters must be replaced upon construction comple-
tion.
• All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
in accordance with these installation instructions.
EQUIPMENT MAY EXPERIENCE PREMATURE COM-
PONENT FAILURE AS A RESULT OF FAILURE TO FOL-
LOW THE ABOVE INSTALLATION INSTRUCTIONS.
FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-
STRUCTIONS VOIDS THE MANUFACTURER'S EQUIP-
MENT LIMITED WARRANTY. LENNOX DISCLAIMS
ALL LIABILITY IN CONNECTION WITH INSTALLER'S
FAILURE TO FOLLOW THE ABOVE INSTALLATION IN-
STRUCTIONS.

Advertisement

Table of Contents
loading

Table of Contents