Pentair KEYSTONE EPI-2 Installation And Maintenance Instructions Manual page 19

Quarter-turn electric actuator
Table of Contents

Advertisement

Keystone ePi-2 quarter-turn electric actuator
InstallatIon and MaIntenance InstructIons
6.2.14 blinker / Local selector configuration
Default configuration for Blinker / Local
selector relay is off (always open)
in Blinker configuration, during actuator
movement the relay changes their status each
500 msecs (Motor running function).
in local selector configuration (with local
interface oM3 installed), the relay is close
when oM3 switch is on reMote, while it is
oPen when oM3 switch is on local.
to configure Blinker or local selector
monitoring function (when oM3 is present):
• Enter set up configuration: move switch SW3
to position on (configuration function)
• Move switch SW4 to position 4
• Move switch SW6 to position 1 (Blinker) or 2
(local selector)
• Confirm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on
for confirmation
• Exit set up configuration (move switch
sW3 to position 1) or proceed with the next
parameter
6.3 Configuration of the epi-2 by a
pda / pC and 'a Manager' softWare
if one of the optional module oM1, oM9 or
oM11 is installed on the ePi-2 and this card
features Bluetooth interface, the actuator
configuration can be performed by means of
the 'a Manager' software installed on the PDa
or Pc.
Only Blinker / Local Selector relay cannot be
configured by means 'a Manager' software.
the relevant instruction and operating Manual
is available with the 'a Manager' software.
Warning
The controls available via Bluetooth allow full
actuator operability at a distance. Pentair will not
accept any responsibility for damages or injuries
caused by an improper use of your Bluetooth PDA.
6.4 hardWare Configuration for
Monitor reLay
the Monitor relay indicates the followings
failures:
• Loss of power
• Stop by Torque out of limits
• Direction failure
• Temperature too high
• Position sensor failure
• Local control panel with selector in local
position
• Valve jammed
• Hardware malfunction
• Alarm on the local control panel (if present)
• Stroke failure
the Monitor relay contacts can be set as
close or oPen by changing the welding of
JuMPer J1 on logic board.
as a default setting, pins 2 and 3 are welded
together, and the Monitor relay contact
operates as follows:
- contact close in normal condition with relay
energized, and oPen in case of malfunction
(relay is de-energized).
in case of request, if contact must be oPen
in normal condition and close in case of
malfunction, the contact of JuMPer J1 must be
modified welding pins 1 and 2 together.
Warning
Configuration of Monitor Relay by means
JUMPER J1 is a hardware configuration. For this
reason, to configure Monitor Relay is mandatory
manage actuator without power supply.
19