10.2 Optional Parts

10.2.1 AS-i Module Catalog No. 3RW3400-0DC88
This AS-i Communications Interface Module, shown in diagram
form in figure 1, can be used with any SIKOSTART 3RW34 con-
troller. The AS-i unit allows the controller to be a slave to an AS-
i master.
An instruction guide furnished with the module
describes installation, wiring and operation.
10.2.2 Lug Kits
The following spare parts are only available in the US.
For parts outside the US and Canada please contact Technical
Support @ +49(0) 9131 74 3833
Email: NST.Technical-Support@ERL7 .siemens.de
Table 11 lists lug kits for use with the SIKOSTART 3RW34 con-
trollers. Each kit provides a method of adapting a controller for
use with aluminum or copper power wiring. One kit contains
lugs for either the line or load side of the controller. Two kits are
required to add lugs to both line and load terminals.
Figure 30 shows a lug in position for mounting to the terminal.
The table 11 Lug Hardware Torque column indicates the torque
required for the screw that secures the lug to the controller ter-
minal. The Wire Size Range column lists the wire sizes that the
lug can accommodate. Table 3 in this manual indicates the
torque required for the set screw that secures the wire in the
lug.
Complete installation instructions are furnished with each

lug kit.

Note:
Mount lug under terminal as shown.
Siemens Energy & Automation, Inc.
Figure 30
Table 11 - Lug Kits
Wye
Operational
Lug Kit
Current
Part
Rating
Number
35, 57 , 69,
80 & 105
91D81755011
131 & 195
91D81755012
248
91D81755013
361
91D81755016
480 - 720
91D81755014
960
91D81755015
Torque required for power terminals set screws 75vC wire, alu-
minum/copper.
Wire Size
(AWG or MCM)
6 to 4
3 to 2
1
1/0 to 2/0
3/0 to 4/0
250 to 400
500 to 600
10.2.3 Overload Relays
The standard SIKOSTART Controller does not include overload
protection. Please refer to SFPC-06000 for overload selection or
contact Technical Support at the number printed on the back
cover of this manual.
Lug
Hardware
Torque
Wire Size
(lb-in.)
Range
2/0 to #
75
14 AWG
275
350 MCM
to #6 AWG
275
(1) 600 MCM
to #6 AWG
or (2) 250 MCM
to #1/0
275
(2) 350 MCM
to #4 AWG
275
(3) 350 MCM
to #6 AWG
275
(4) 350 MCM
to #6 AWG
Torque
Lb - in
100
125
135
150
225
290
335
45