Follow these instructions to install the time switch.
1.
Open the time switch enclosure door.
2.
Remove and retain the screw that secures the plastic insulator.
3.
Lift the left side of the plastic insulator and pivot away to expose the terminal strip.
4.
Press the latch at the top of the enclosure and pull out the mechanism from the
enclosure.
5.
Choose and remove the selected knockout(s) from the enclosure.
NOTE: There are five 1/2 inch to 3/4 inch combination knockouts available. There are
two on the bottom of the enclosure, one on each side, and one on the rear. If a 3/4
inch knockout is needed, remove the 1/2 inch knockout first, then the 3/4 knockout.
6.
Place the enclosure in the desired location providing space for the enclosure door to
swing open fully.
7.
Securely mount enclosure using provided mounting holes.
8.
Use appropriately rated fittings for the installation.
9.
Snap the mechanism back into the enclosure.
10. Strip 1/2 inch off the supply and load wires. Use AWG #14 - #8 copper conductors
rated at least 105ºC. Torque to 15.6 lbf-in.
11. Connect the wires to the proper terminals on the time switch and tighten the screws
firmly (See wiring diagrams).
12. Connect ground wire to grounding terminal at the bottom of metal enclosures.
13. Return the insulator to its original position and replace the screw.
14. Close enclosure door.
15. Apply power to the time switch.
Latch location
Tilt top forward
1/2 inch
Wiring Diagrams
TIMER POWER
AC IN
L1
L2/N
POWER TO TIMER
120/208/240/277 VAC
(AUTO VOLTAGE, NO JUMPERS REQUIRED)
TIMER
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
POWER
AC IN
NO-1 COM1 NO-2 COM2 NO-3 COM3 NO-4 COM4
L1
LOAD 1
LOAD 2
L2
TIMER CONFIGURATION FOR TWO 208/240 VAC DPST
OUTPUT CONFIGURATION: SIM - CIRCUIT 1 AND 2
OUTPUT CONFIGURATION: SIM - CIRCUIT 3 AND 4
TIMER
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
POWER
AC IN
NO-1 COM1 NO-2 COM2 NO-3 COM3
NO-4
COM4
L1
L2/N
LOAD 1
LOAD 2
LOAD 3
N
L3
N
L4
L5 L6
TIMER CONFIGURATION FOR COMBINATION MODE
OUTPUT CONFIGURATION: IND - CIRCUIT 1 AND 2 (120/277 VAC LOAD)
OUTPUT CONFIGURATION: SIM - CIRCUIT 3 AND 4 (208/240 VAC LOAD)
TIMER
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
POWER
NO-1 COM1 NO-2 COM2 NO-3 COM3 NO-4 COM4
AC IN
L1
L2/N
LOAD2
LOAD3
LOAD1
N
L3
N
TIMER CONFIGURATION FOR COMBINATION MODE
OUTPUT CONFIGURATION: PUL - CIRCUIT 1 AND 2 (BELL RINGING)
OUTPUT CONFIGURATION: IND - CIRCUIT 3 AND 4
TIMER
CIRCUIT 1
CIRCUIT 2
POWER
COM2
AC IN
NO-1
COM1
NO-2
L1
L2/N
LOAD 1
LOAD 2
LOAD 3
N
L3
N
L4
4 - INDIVIDUAL 120/277 VAC LOADS
OUTPUT CONFIGURATION: IND - CIRCUIT 1 AND 2
OUTPUT CONFIGURATION: IND - CIRCUIT 3 AND 4
TIMER
CIRCUIT 1
CIRCUIT 2
POWER
AC IN
NO-1
COM1
NO-2
COM2
L1
L2/N
TIMER CONFIGURATION FOR TWO CONTACTOR CONTROLS
OUTPUT CONFIGURATION: PUL - CIRCUIT 1 AND 2
OUTPUT CONFIGURATION: PUL - CIRCUIT 3 AND 4
TIMER
CIRCUIT 1
CIRCUIT 2
POWER
AC IN
NO-1
COM1
NO-2
COM2
L1
L2/N
LOAD 1
LOAD 2
L3 L5
TIMER CONFIGURATION FOR COMBINATION MODE
OUTPUT CONFIGURATION: SIM - CIRCUIT 1 AND 2 (208/240 VAC LOAD)
OUTPUT CONFIGURATION: IND - CIRCUIT 3 AND 4 (120/277 VAC LOAD)
TIMER
CIRCUIT 1
CIRCUIT 2
POWER
AC IN
NO-1
COM1
NO-2
COM2
L1
L2/N
LOAD1
240VAC
L4
TIMER CONFIGURATION FOR COMBINATION MODE
OUTPUT CONFIGURATION:PUL - CIRCUIT 1 AND 2 (BELL RINGING)
OUTPUT CONFIGURATION: SIM - CIRCUIT 3 AND 4 (208/240 VAC LOAD)
CIRCUIT 3
CIRCUIT 4
NO-3
COM3
NO-4 COM4
LOAD 4
N
L5
N
L6
CIRCUIT 3
CIRCUIT 4
NO-3
COM3
NO-4
COM4
CIRCUIT 3
CIRCUIT 4
NO-3
COM3
NO-4 COM4
LOAD 3
N
L6
N
L7
CIRCUIT 3
CIRCUIT 4
NO-3
COM3
NO-4
COM4
LOAD 2

Advertisement

loading

This manual is also suitable for:

Et2845crEt2845cpEt2845