Installation

Follow these instructions to install the timer switch.
1.
Open the Smart Wi-Fi Timer enclosure door.
2.
Choose and remove the selected ½" to ¾" combination knockout(s) from the enclosure.
3.
Place the enclosure in the desired location providing space for the enclosure door to swing open fully.
Note: Prior to installation, it is recommended to check your Wi-Fi signal strength at the desired installation location. A weak
signal strength could create intermittent Wi-Fi connection issues.
4.
Mount the enclosure using hardware appropriate for the mounting surface (e.g., brick, concrete, drywall). We recommend using
two of the several 5 mm raised mounting locations in the back of the enclosure rather than the single-location hang slot.
(hardware not included) (Figure 1)
Note: Separation plate included in product for class 2 connections. Must not be removed.
Figure 1
1/2", 3/4" DIA KO
(5 PLACES)
5.
Use appropriately rated fittings for the installation.
6.
Strip ½" off the supply and load wires. Use AWG #14 - #8 copper conductors rated at least 105º C. Torque 10.6 to 15.6 Lb-In.
7.
Connect the wires to the proper terminals on the Wi-Fi timer and tighten the screws firmly (See wiring diagram figures A and B).
8.
Close enclosure door.
9.
Apply power to the time switch.
10. Install ¼" Padlock thru hasp to secure if desired. (lock not included)
11. Device configuration are done using the Intermatic Connect mobile app. (available via the App Store and Google Play)

Wiring Diagrams

Figure A: 3 Circuit - 3xSPDT or 1xDPDT + 1xSPDT, Circuit 1 and Circuit 2 can be paired for DPDT applications
Figure B: 2 Circuit - 2xSPDT or 1xDPDT, Circuit 1 and Circuit 2 can be paired for DPDT applications
Figure C: Example of wiring a photocontrol, occupancy/vacancy sensor, or a single pole switch requiring a neutral.
120-277 VAC (For 277 VAC see note #1)
Figure A
TIMER
POWER
REMOTE INPUTS
SW1
SW2
SW3
AC IN
L1
L2/N
POWER TO TIMER
120/208/240/277 VAC
(AUTO VOLTAGE,
NO JUMPER REQUIRED)
Note 1: If using 277 VAC for the remote input terminals, Inputs 1 and 3
or Input 2 alone may be used on model PE733P
Note 2: For DPDT operations Circuit 1 and Circuit 2 will be paired
LOCKING HASP
4.80"
2.56"
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
NC-1
NO-1 COM1
NC-2
NO-2
COM2
NC-3
NO-3
4.00"
120-277 VAC (For 277 VAC see note #3)
Figure B
TIMER
POWER
REMOTE INPUTS
COM3
SW1
SW2
AC IN
L1
POWER TO TIMER
120/208/240/277 VAC
(AUTO VOLTAGE,
NO JUMPER REQUIRED)
Note 3: If using 277 VAC for the remote input terminals,
Input 1 or Input 2 alone may be used on model PE723P
CIRCUIT 1
CIRCUIT 2
NC-1
NO-1 COM1
NC-2
NO-2
COM2
L2/N
Figure C
120-277V
REMOTE INPUT
WHITE
N/L2
L1
POWER TO
PHOTO CONTROL
OR OCC SENSOR