Bryant Preferredt Series Installation Instructions Manual page 31

Ac / hp thermostat
Table of Contents

Advertisement

Option 11 — Deadband Setting Between Heat & Cool
This option is not available on Heat Only and Cool Only systems. This selection is
to allow the installer to choose how much differential exists between the heating
and cooling setpoints. Allowable selections are 1- 6.
Default is 2.
Option 12 — Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery
time. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is programmed.
Not available with non- programmable thermostats or when thermostat is
configured as non- programmable.
Default is 90.
Option 13 — Room Air Temperature Offset Adjust
The number of degrees to be added to the displayed temperature to calibrate or
deliberately miscalibrate the measured room temperature ( - 5 to +5_).
Default is 0.
Option 15 — Enable Auto Mode
This selection is not available if the thermostat is configured as Heat Only or Cool
Only in Option 1. This allows the homeowner to select auto changeover mode in
addition to heat and cool. This allows the thermostat to automatically change
between heating mode and cooling mode when sufficient demand for heating or
cooling exists.
On — Auto mode is available.
OF — Auto mode is not available.
Default is On.