Carrier 619FB Service Manual page 35

High---wall ductless split system, sizes 009 to 018
Hide thumbs Also See for 619FB:
Table of Contents

Advertisement

2. Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of the outdoor unit).
Main detection points:
S
Detect of the voltage of L1 and L2 terminals of the wiring board is between 210AC- -240AC by alternating voltage meter.
S
Is reactor (L) well connected? Is connection wire loosened or pull- -out? Is reactor (L) damaged?
Malfunction diagnosis process:
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Voltage higher than 200V?
No
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
Voltage within
210VAC~250VAC?
Yes
Shut down the power and wait 20 mi
use DC voltmeter to measure the voltage
on the two ends of capacitor (test3), until
the voltage is lower than 20V
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
reactor L is normal?
Yes
Replace the control
panel AP1
End
Fault with the voltage
testing circuit on
Yes
Y
control panel AP1
N
Shut down the power
and repair the power
No
N
supply to restore the
range
210VAC~250VAC
Y
nutes; or
Connect the reactor
Laccording to Elec-
No
N
trical Wiring Diagr-
am correctly
Y
Fig. 38 – Troubleshooting
Replace the control
panel AP1
power on and
restart the unit
No
N
Re-energize and
If the fault is
turn on the unit
eliminated?
No
N
35
If the fault is
Yes
Y
eliminated?
Yes
Y