Menu 2: Advanced Setup
PROJECT
PARAMETER
MA LO SET
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
SD DMPR POS
DCVCAL ENA
MAT T CAL
0.0
OA T CAL
2.0
OA H CAL
RA T CAL
4.0
RA H CAL
DA T CAL
0.0
2SP FAN DELAY
PARAMETER
DEFAULT
VALUE
VALUE
45°F (7°C)
35 to 55°F (2 to 13°C);
incremented by 1°
CLO
CLO or MIN
0ppm
0 to 500 ppm;
increment by 10
2000ppm
1000 to 3000 ppm;
increment by 50
2.0h
0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 h
or OFF
CLO
CLO or OPN
MAN
MAN (manual)
1.0°F (or °C)
± 2.5°F (± 1.4°C)
3.0°F (or °C)
± 2.5°F (± 1.4°C)
0% RH
± 10% RH
5.0°F (or °C)
± 2.5°F (± 1.4°C)
0% RH
± 10% RH
1.0°F (or °C)
± 2.5°F (± 1.4°C)
5 minutes
0 to 20 minutes in
1 minute increments
PARAMETER
RANGE AND
INCREMENT
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and
alarm if temperature at SAT location falls below setup value)
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO =closed
MIN = MIN POS or VENTMAX
CO
ppm level to match CO
2
CO
ppm span to match CO
2
COOLING STAGE 3 DELAY
Delay after stage 2 for cool has been active. Turns on second
stage of cooling when economizer is first stage and mechanical
cooling is second.
Function NOT AVAILABLE with 2-speed mode
Turns on the DCV automatic control of the dampers. Resets
ventilation.
SUPPLY AIR TEMPERATURE CALIBRATION
Allows the operator to adjust for an out of calibration supply air
temperature (SAT) sensor.
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows the operator to adjust for an out of calibration outside air
temperature (OAT) sensor
OUTSIDE AIR HUMIDITY CALIBRATION
Allows the operator to adjust for an out of calibration of outside
air enthalpy sensor
RETURN AIR TEMPERATURE CALIBRATION
Allows the operator to adjust for an out of calibration return air
temperature (RA) sensor
RETURN AIR HUMIDITY CALIBRATION
Allows the operator to adjust for an out of calibration return air
enthalpy sensor
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows the operator to adjust for an out of calibration discharge
air temperature (DAT) sensor
TIME DELAY ON SECOND STAGE ECONOMIZING
While in the Economizing mode, this is the delay between ther-
mostat Y2 call and Y1-O output to mechanical cooling stage, to
allow high speed fan operation to attempt to cool space first.
64