Universal Control Systems
Control installation
EG-30 through EG-75 water boilers without tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause se-
vere personal injury, death or substantial
property damage.
Figure 2
EG-30 through EG-75 water boilers without tankless heaters
Part Number 550-142-304/1220
(Continued)
1. Mount and wire controls per wiring diagram, page 9, and Figure 2.
a. Attach junction box inside left jacket panel with #8-32 x ½" machine screws
provided.
b. Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.