Troubleshooting – (EG water boilers)
– Spark-ignited pilot – TSTAT/CIRC & POWER light flashing
CHART 2
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲ , follow the instructions.
Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Disconnect the two external wires connected to the boiler
thermostat leads. (two (2) black low voltage leads in J-box).
• Connect a voltmeter across the two incoming wires.
Close each thermostat, zone valve and relay in the external
circuit one at a time and check the voltmeter reading across
the wires.
• There should NEVER be a voltage reading.
• Leave external boiler thermostat connection wires
disconnected from boiler.
• Trouble shoot the external thermostat circuit until you
find the source of the stray voltage. (Pay close atten-
tion to the wiring connections to 3-wire zone valves.)
• Correct the problem and repeat voltmeter test above,
verifying there is no longer a voltage reading under any
condition in the external thermostat circuit.
• Boiler should now operate per the normal sequence of
operation shown in Figure 1, page 6.
Part Number 550-142-304/1220
– Usually indicates 48 VAC on thermostat circuit (stray voltage) –
Did you find a voltage across the two external thermostat circuit wires?
Yes
continued
• If a voltage does occur under any condition, check and cor-
rect the external wiring. (This is a common problem when
using 3-wire zone valves.)
• Once the external thermostat circuit wiring is checked and
corrected if necessary, reconnect the external thermostat
circuit wires to the boiler thermostat wires and allow the
boiler to cycle.
If no voltage is found under any condition of the external
thermostat circuit, connect the two boiler thermostat
connection leads together (or jumper the boiler aquastat
T-T terminals).
Turn off power to the boiler for 1 minute.
Turn on power and allow boiler to cycle.
Do the TSTAT and POWER lights still flash?
No
No
Yes
Replace control module.
Retest.