5
REPLACEMENT OF BASE UNIT AND EXTENSION CABLE
(3) Extension base unit (type requiring power supply module)
(a) Comparison between A1S65B(-S1) and Q65B
Item
Number of mountable I/O
modules
Extension base unit
Internal current
consumption (5VDC)
Mounting hole size
External dimensions
Panel installation
dimensions
(b) Comparison between A1S68B(-S1) and Q68B
Item
Number of mountable I/O
modules
Extension base unit
Internal current
consumption (5VDC)
Mounting hole size
External dimensions
Panel installation
dimensions
5.2.2 Comparison of extension cable specifications
Item
Cable length
5
- 7
AnS/QnAS series
A1S65B
A1S65B-S1
5 modules can be mounted.
Cannot be
Can be
connected.
connected.
-
6 bell-shaped hole
(For M5 screw)
130(H)315W)28(D)mm
295 110mm
AnS/QnAS series
A1S68B
A1S68B-S1
8 modules can be mounted.
Cannot be
Can be
connected.
connected.
-
6 bell-shaped hole
(For M5 screw)
130(H)420W)28(D)mm
400 110mm
AnS/QnAS series
AnS main-AnS
extension
0.055m
A1SC01B
0.33m
A1SC03B
0.45m
–
0.6m
–
0.7m
A1SC07B
1.2m
A1SC12B
3.0m
A1SC30B
5.0m
–
6.0m
A1SC60B
10.0m
–
Model
Q series
Q65B
Can be connected.
0.11A
M4 screw hole or 4.5 hole
(For M4 screw)
98(H) 245(W)44.1(D)mm
222.5
80mm
Model
Q series
Q68B
Can be connected.
0.12A
M4 screw hole or 4.5 hole
(For M4 screw)
98(H)328(W)44.1(D)mm
306
80mm
Model
AnS main-A
Q series
extension
–
–
–
–
A1SC05NB
QC05B
–
QC06B
A1SC07NB
–
–
QC12B
A1SC30NB
QC30B
A1SC50NB
QC50B
–
–
–
QC100B
Precautions for replacement
For precautions for replacement,
refer to Section 5.3.1.
The upgrade tool (base adapter)
with existing mounting holes is
available.
Precautions for replacement
For precautions for replacement,
refer to Section 5.3.1.
The upgrade tool (base adapter)
with existing mounting holes is
available.
Precautions for replacement
For precautions for replacement,
refer to Section 5.3.2.