Specifying The Number Of Input/Output Points; How To Specify The Number Of Input/Output Points - Panasonic FP2 S-LINK Technical Manual

Hide thumbs Also See for FP2 S-LINK:
Table of Contents

Advertisement

3.2 Specifying the Number of Input/Output Points

3.2.1 How to Specify the Number of Input/Output Points

The number of input points and number of output points for the S-LINK are specified using the MODE
switch.
The number can be selected as shown in the table below.
No.
Input [No. of points]
− [0]
0
− [0]
1
− [0]
2
3
X(n)0 to X(n+1)F [32]
4
X(n)0 to X(n+1)F [32]
5
X(n)0 to X(n+1)F [32]
6
X(n)0 to X(n+3)F [64]
7
X(n)0 to X(n+3)F [64]
8
X(n)0 to X(n+3)F [64]
9
X(n)0 to X(n+7)F [128]
− [0]
A
B
X(n)0 to X(n+1)F [32]
C
X(n)0 to X(n+5)F [96]
D
X(n)0 to X(n+5)F [96]
E
X(n)0 to X(n)F [16]
F
X(n)0 to X(n+7)F [128]
Note:
• No. 1, No. 7 and No. D cannot be used. If they are set, an error (E34: I/O status error) occurs in the
control unit.
• I/O numbers are determined based on the position of the slot used for installation.
• If the MODE switch is changed during the operation, an error occurs in the FPΣ control unit.
• The contents of the settings for No. 9 and No. F are the same (either one may be selected).
FPΣ
Output [No. of points]
Y(n)0 to Y(n+1)F [32]
Y(n)0 to Y(n+3)F [64]
Y(n)0 to Y(n+7)F [128]
− [0]
Y(n)0 to Y(n+1)F [32]
Y(n)0 to Y(n+3)F [64]
− [0]
Y(n)0 to Y(n+1)F [32]
Y(n)0 to Y(n+3)F [64]
− [0]
Y(n)0 to Y(n+5)F [96]
Y(n)0 to Y(n+5)F [96]
− [0]
Y(n)0 to Y(n+1)F [32]
Y(n)0 to Y(n)F [16]
− [0]
S-LINK
No. of
Input
Output
address
address
points
0 to 31
0 to 63
0 to 127
0 to 31
0 to 31
32 to 63
0 to 31
32 to 95
0 to 63
0 to 63
64 to 95
0 to 63
64 to 127
0 to 127
0 to 95
0 to 31
32 to 127
0 to 95
0 to 95
96 to 127
0 to 15
16 to 31
0 to 127
No. of
Total
input
output
No. of
points
points
0
32
32
0
64
64
0
128
128
32
0
32
32
32
64
32
64
96
64
0
64
64
32
96
64
64
128
128
0
128
0
96
96
32
96
128
96
0
96
96
32
128
16
16
32
128
0
128
3-3