Mitsubishi Electric CITY MULTI CMB-P-V-G Series Installation Manual page 2

Air-conditioners for building application indoor unit bc controller
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
2
2.1
[Fig. 2.1.1]
[Fig. 2.2.2]
A
B
A
B
118
362
53
Model name
A
CMB-P104V-G
648
CMB-P105V-G
648
CMB-P106V-G
648
CMB-P108V-G
648
CMB-P1010V-G
648
CMB-P1013V-G
1098
CMB-P1016V-G
1098
Item
Total piping length
Longest piping length
Between outdoor unit and
BC controller
Between indoor units and BC controller
Between
Above outdoor unit
indoor and
outdoor units
Below outdoor unit
Between indoor units and BC controller
Between indoor units
3
[Fig. 3.2.1]
B
A
C
D
1
2
2
[Fig. 2.2.1]
77
A
77
A On the side of outdoor unit piping
B On the side of indoor unit piping
Piping portion
Allowable value
A+B+a+b
Below 300*1
+c+d+e
A+e
Below 150
Below 110
A
(Below 60)*1
e
Below 40
H
Below 50
H1
Below 40
Below 15
h1
(Below 10)*3
Below 15
h2
(Below 10)*3
3.2
D
1 Hanging method
2 Installing-on-the-floor method
C
A: Min.30 mm
B
A Hanging bolt ø10 (field supply)
B Nut (field supply)
E
C Washer (field supply)
D Double nuts (field supply)
E Anchor bolt M10 (field supply)
200
<A>
A
450
C
B
D
INDOOR UNIT SIDE
200
A
A Inspection hole
B On the side of outdoor unit piping
C Control box
D On the side of indoor unit piping
*1 Dimensions with which pipe connection can be handled at site
[Fig. 2.3.1]
A Outdoor unit
(Unit: m)
C Indoor unit
E Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G Branch pipe (for Y Series) CMY-Y102S-G
H Combined pipe (CMY-R160-J: optional)
I Less than 110 m
K Up to three units for 1 branch hole
Total capacity: less than 140 (but same in cooling/heating mode)
L Less than h1=15 m (10 m or less for 200, 250 unit type)
M Less than h2=15 m
Notes:
*1 Please refer to the figure "Allowable Pipe Length" below when the total
piping length exceeds 300 m.
*2 Please refer to the figure "Distance between BC controller and farthest
indoor unit" when the distance between BC controller and farthest in-
door unit exceeds 40 m.
*3 10 m or less, with indoor units with model numbers of 200, 250.
Allowable pipe length
400
350
300
250
200
30
40
50
60
Distance between outdoor
unit and BC controller (m)
2.2
<B>
B
Model name
CMB-P104V-G
CMB-P105V-G
CMB-P106V-G
CMB-P108V-G
CMB-P1010V-G
CMB-P1013V-G
CMB-P1016V-G
2.3
A
I
A
B
J
H
a
G
C
b
B
c
d
C
C
D
K
B BC controller
D More than 81
J Less than 40 m
Distance between BC controller
and farthest indoor unit
70
60
50
40
30
20
10
0
0
70
80
90
100
110
Height difference between
BC controller and farthest
indoor unit (m)
<A> Top view
<B> Front view
A
648
648
648
648
648
1098
1098
e
C
C
5
10
15