6 LCCF_EnetScanner block
Valid
FALSE
FALSE
FALSE
FALSE
FALSE
EtherNet/IP Scanner
Entry-ID: 109782314,
V1.1.0,
Busy
Error
Status
Code
(in hex)
FALSE
TRUE
16#82x8
FALSE
TRUE
16#82x9
FALSE
TRUE
16#86xA
FALSE
TRUE
16#86xB
FALSE
TRUE
16#86xC
04/2021
Cause
smaller than
size.
configured for
adapter[x]
Parameterized
Adjust the configured
output buffer is
O→T direction data
smaller than
size.
configured for
adapter[x]
Parameterized
Adjust the configured
configuration data
configuration data size.
buffer is smaller
than configured
for adapter[x]
Incompatible
The configured T→O
buffer types for
buffer type is
adapter [x]
incompatible to the
parameterized Input
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.
Incompatible
The configured O→T
buffer types for
buffer type is
adapter [x]
incompatible to the
parameterized Output
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.
Incompatible
The configured
buffer types for
configuration data
adapter [x]
buffer type is
incompatible to the
parameterized
configuration data
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.
Remedy
40