4 Configuration/Engineering
Step
4.
Open the EDS file of the second
adapter with you text editor program
(e.g. Notepad).
Note the relevant data from the
differerent sections
5.
Transfer the noted data to the
EnetIOSystem data block
EtherNet/IP Scanner
Entry-ID: 109782314,
V1.1.0,
Instruction
04/2021
Result
The following data are used in this
application example
From sections
[Device]
•
VendorCode = 1251
•
ProductType = 12
•
ProductCode = 1200
•
Revision = 1.004
[Params]
•
Output Size = 64 Bytes
•
Input Size = 64 Bytes
•
RPI = 25 ms (25.000µs)
[Connection Manager]
•
Instance ID = 104 (68hex)
•
OT Assembly ID = 102 (66hex)
•
TO Assembly ID = 101 (65hex)
as a result, the EnetIoSystem should
look like the below:
26