Download Print this page

Viking M Installation page 4

Standard response dry pendent sprinklers
Hide thumbs Also See for M:

Advertisement

Sprinkler 101 d
Thread Size
NPT
BSP
Style
1"
Adjustable
25 mm
Standard
25 mm
1"
Adjustable
25 mm
Recessed
25 mm
1"
25 mm
Plain Barrel
25 mm
Thread Size
NPT
BSP
Style
1"
Adjustable
25 mm
Standard
1"
Adjustable
25 mm
Recessed
1"
Plain Barrel
25 mm
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C), and 286 °F
(141 °C)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F (93 °C)
1
Base part number is shown. For complete part number, refer to Viking's current price schedule.
2
This table shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for
any additional approvals.
3
K-factor applies for standard lengths ("A" Dimensions indicated above). Metric K-Factor shown is for use when pressure is measured in kPa.
When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
4
Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. II.
5
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
6
Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. XV.
7
Metric K-Factors shown are for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
should be given to employment of a fire
patrol in the effected area.
1. Remove the system from service,
drain all water, and relieve all pres-
sure on the piping.
2. Using the special sprinkler wrench,
remove the old sprinkler and install
the new unit. Care must be taken to
ensure that the replacement sprin-
kler is the proper model and style,
with the appropriate "A" dimension,
orifice size, temperature rating, and
response characteristics.
3. Place the system back in service
and secure all valves. Check for and
repair all leaks.
E. Sprinkler systems that have been sub-
jected to a fire must be returned to ser-
vice as soon as possible. The entire
system must be inspected for damage
and repaired or replaced as necessary.
Sprinklers that have been exposed to
corrosive products of combustion or
high ambient temperatures, but have
not operated, should be replaced. Re-
fer to the AHJ for minimum replace-
ment requirements.
Replaces page 101 a-d, dated May 13, 2005
(revised the K-Factor graph).
TECHNICAL DATA
Approval Chart
Standard Response Dry Pendent Sprinklers
Sprinkler Description
1
Base Part Number
SIN
07740
VK154
07854
VK154
09341
VK155
06530
VK158
07853
VK158
09342
VK159
07852
VK150
07855
VK150
09343
VK151
Sprinkler Description
1
Base Part Number
SIN
12810
VK163
12813
VK163
12811
VK164
12814
VK164
12741
VK166
12812
VK166
Figure 4: K-Factor/Length Graph for Large Orifice Dry Pendent
Sprinklers for lengths from 20" to 48" (508 mm to 1 219 mm).
Standard Orifice
Order Length
3
Nominal K-factor
U.S.
metric
Inches
5.6
8,1
8,1
5.6
8,1
8,1
5.6
8,1
8,1
Large Orifice
Order Length
7
Nominal K-factor
Inches
8.0 U.S. (11,5
metric) for lengths
up to 20". For
lengths exceeding
20", refer to Fig. 4
on page 101 d.
Approved Finishes and "A" Dimensions
®
1- Chrome-Enloy
or White Polyester sprinkler with a Chrome-Enloy
and Escutcheon with "A" dimensions 1-1/2" to 45-1/2" (38,1 mm to 1 156 mm)
®
2 - Chrome-Enloy
with "A" dimensions 1-1/2" to 45-1/2" (38,1 mm to 1 156 mm)
®
3 - Chrome-Enloy
or White Polyester with "A" dimensions 3-1/4" to 47-1/2"
(82,5 mm to 1 207 mm)
®
4 - Chrome-Enloy
or Brass with "A" dimensions 3" to 47" (76,2 mm to 1 194 mm)
Footnotes
Lengths exceeding the standard length are available, with no approvals,
on a "made-to-order" basis. Contact the manufacturer.
Metric K-Factors are for use when pressure is measured in kPa.
When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0.
Note: For lengths up to 20" (508 mm), the nominal
K-Factor is 8.0 U.S. (11,5 metric).
September 16, 2005
STANDARD RESPONSE
DRY PENDENT SPRINKLERS
Temperature
Finish
Escutcheon (if applicable)
A1X
Listings and Approvals
Increment
5
mm
cULus
FM
½"
12,7
A1
A2
½"
12,7
A1
A2
½"
12,7
¼"
6,35
B3
B3
¼"
6,35
B3
B3
¼"
6,35
½"
12,7
A4
A4
½"
12,7
A4
A4
½"
12,7
Listings and Approvals
Increment
5
mm
cULus
FM
½"
12,7
A1
½"
12,7
A1
¼"
6,35
B3
¼"
6,35
B3
½"
12,7
A4
½"
12,7
A4
Form No. F_071591
KEY
2
4
NYC
LPCB
A1
A2
B3
B3
A4
A4
2
6
NYC
LPCB
A1
A1
B3
B3
A4
A4
®
Sleeve

Advertisement

loading

This manual is also suitable for:

Vk150Vk151Vk154Vk155Vk158Vk159 ... Show all