Viking M Installation page 2

Standard response dry pendent sprinklers
Hide thumbs Also See for M:

Advertisement

Sprinkler 101 b
ESCUTCHEON MATERIALS
1. Adjustable Standard Dry Escutcheons:
Brass UNS-C26000 or UNS-C26800
2. Recessed Dry Escutcheons: Cold
Rolled Steel UNS-G10080
AVAILABLE FINISHES
Recessed Style: Chrome-Enloy
pending) or White Polyester
Standard Adjustable: Chrome-Enloy
White Polyester sprinkler with a Chrome-
®
Enloy
Sleeve and Escutcheon
Plain
Barrel
Style
(sprinkler
Chrome-Enloy
®
or Brass
SPRINKLER TEMPERATURE RATINGS
Refer to the chart on page 101 a.
ACCESSORIES
Dry Sprinkler Wrenches:
A. Standard: Part No. 07297W/B
B. Recessed: Part No. 07565W/B†
†Requires a separate ½" ratchet (not available from
Viking).
Sprinkler Guard: Chrome, with no listings
or approvals, for installation on dry pen-
dent sprinklers manufactured after May
1994 only (Part Number 08954).
Replacement Escutcheons:
1. Adjustable Standard Dry Escutcheon:
Base Part Number 07741
2. Recessed Dry Escutcheon
Cup: Base Part Number 05459A
5. ORDERING INFORMATION
For proper shipment, specify model, orifice
size, finish, temperature rating, escutcheon
type, and length ("A" dimension). Dry pen-
dent sprinklers are ordered in specific
For "A" Dimension: 1. Determine distance from the face of the tee to the finished ceiling.
2. Round to nearest ½" (12,7 mm) between 1-1/2" and 45-1/2" (38,1 mm and 1 156 mm).
NOTE: The deflector will be located approximately 3-7/16" (87,3 mm) below the ceiling
Finished Ceiling
1-1/2" (38,1 mm)
diameter
(77,8 mm)
Figure 1:
TECHNICAL DATA
lengths noted as the "A" dimension (see Fig-
ures 1 through 3). The "A" dimension is the
distance from the face of the fitting (tee) to
the desired finished ceiling location. The dry
pendent sprinkler must be ordered and man-
ufactured specifically for one of three styles
of installation: with the adjustable recessed
®
(patents
escutcheon (see Figure 3), with the adjust-
®
able standard escutcheon (see Figure 1), or
or
with the plain barrel (see Figure 2). Escutch-
eons slip on from below the ceiling to allow
installation of the sprinkler prior to ceiling in-
only):
stallation. For limits of adjustment for the re-
cessed escutcheon, see Figure 3. Details
and limits of adjustment for the standard ceil-
ing escutcheon style, with 2" (51 mm) of ad-
justment, are shown in Figure 1.
6. INSTALLATION
WARNING: Viking sprinklers are manu-
factured and tested to meet the rigid re-
quirements of approving agencies. The
sprinklers are designed to be installed in
accordance with recognized installation
standards. Deviation from the standards or
any alteration to the sprinkler after it leaves
the factory including, but not limited to,
painting, plating, coating, or modification,
may render the sprinkler inoperative and
will automatically nullify the approval and
any guarantee made by Viking.
A. Viking sprinklers are to be installed in
accordance with the latest edition of
Viking technical data, the latest stan-
dards of the National Fire Protection
Association, Factory Mutual, Loss
with 1" (25,4 mm) upward and 1" (25,4 mm) downward adjustment.
Minimum ceiling opening
diameter: 1-3/4" (44,45 mm)
Maximum ceiling opening
diameter: 2-1/4" (57 mm).
13/16"
(20,6 mm)
Sleeve finish
matches escutcheon
3-1/16"
Adjustable Standard Dry Pendent Sprinkler with up to 2" (51 mm) of adjustment.
STANDARD RESPONSE
DRY PENDENT SPRINKLERS
Prevention
Pleniere, VdS or other similar organi-
zations, and also with the provisions
of governmental codes, ordinances,
and standards, whenever applicable.
The use of dry sprinklers may be lim-
ited due to occupancy and hazard.
Refer to the AHJ prior to installation.
B. Sprinklers must be handled with care.
They must be stored in a cool, dry place in
their original container. Never install
sprinklers that have been dropped or
damaged in any way. Never install any
glass-bulb sprinkler if the bulb is cracked
or if there is a loss of liquid from the bulb. If
a glass bulb lacks the appropriate amount
of fluid, it should be set aside and returned
to Viking (or an authorized Viking distribu-
tor) for analysis as soon as possible. If the
sprinkler is not returned to Viking, it should
be destroyed. Never install sprinklers that
have been exposed to temperatures in
excess of the maximum ambient temper-
ature allowed. Such sprinklers should be
destroyed immediately.
C. Viking dry pendent sprinklers are not in-
tended for use in corrosive environ-
ments. Use only sprinklers listed for
corrosive environments when subject
to corrosive atmospheres.
WARNING: Viking dry sprinklers are to be
installed in the 1" outlet or run of malleable
or ductile iron threaded tee fittings that
meet the dimensional requirements of
ANSI B16.3 (Class 150), or cast iron
2-7/16"
(62 mm)
min.
Deflector at Minimum
Distance Below Ceiling
4-7/16"
(113 mm)
max.
Deflector at Maximum
Distance Below Ceiling
September 16, 2005
Council,
Assemblee
NOTE:
To locate the deflector
at the minimum distance
below the ceiling, with
no upward adjustment
available, order the dry
pendent sprinkler 1"
(25,4 mm) shorter than
the "A" dimension.
NOTE:
To locate the deflector at
the maximum distance
below the ceiling, with no
downward adjustment
available, order the dry
pendent sprinkler 1"
(25,4 mm) longer than
the "A" dimension.