Siemens SINAMICS S120 Applications Manual page 40

Motor modules booksize parallel connection
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
5.4 Step 2: Creating a drive object
7. A new drive object, e.g. Vector_03 appears in the project navigator.
This is the drive object for the Motor Modules Booksize connected in parallel.
Note
Drive object
The two Motor Modules Booksize are represented by a drive object for Motor Modules
Booksize connected in parallel.
8. In the project navigator, double-click "Configuration" under the drive object.
Check the configuration of the new drive object for the following information:
– The power unit type must contain the entry "Parallel connection".
– The rated current of the power unit must correspond to this value: 2·0.95·rated current of
– The rated power of the power unit must correspond to this value: 2·0.95·rated power of
If you do net get these values, repeat the commissioning from Step 1: Restoring the factory
settings (Page 35).
38
the type of the Motor Modules Booksize connected in parallel
the type of the Motor Modules Booksize connected in parallel
Motor Modules Booksize parallel connection
Application Manual, 01/2020, 6SL3097-5BF00-0BP0