14 Troubleshooting

14.1 Quick guide to troubleshooting

The meter may report or exhibit issues that are caused by installation, wiring, configuration, and process
problems — including external devices, or mechanical issues with the sensor itself.
To identify and resolve problems as effectively as possible, work through the following list of suggestions:
If this is a first installation:
Verify the power wiring and power supply.
Verify the output wiring. The outputs must be powered externally.
Verify the grounding.
Verify cable shielding.
Perform loop tests for each output.
Check the sensor installation and orientation. Ensure that it is appropriate for your application.
Ensure that the installation meets temperature and/or pressure requirements.
Check for active status alerts and follow the recommendations.
If the device appears to be functioning correctly, but the process data is not acceptable, review the
symptoms and suggestions in the following sections:
Density measurement problems
Temperature measurement problems
Gas measurement problems
Concentration measurement problems
If the device appears to be functioning correctly, but the control loop is not performing as expected:
Verify the output wiring.
Ensure that all external devices are operational, are receiving data, and are configured appropriately.
Use sensor simulation to test boundary conditions and system response.
Configuration and Use Manual
Troubleshooting
March 2021