Servicing - Goodman GMEC80 Service Instructions Manual

Two stage furnace with multi-speed ecm motor
Hide thumbs Also See for GMEC80:
Table of Contents

Advertisement

SERVICING

CHECKING VOLTAGE
HIGH VOLTAGE
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRING.
F
SOURCES MAY BE PRESENT.
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove cover from the Junction Box and gain access
to incoming power lines.
With Power ON:
L
INE VOLTAGE NOW PRESENT
2. Using a voltmeter, measure the voltage across the hot
and neutral connections.
NOTE: To energize the furnace, the Door Interlock Switch
must be engaged at this point.
3. No reading - indicates open wiring, open fuse, no
power, or faulty Door Interlock Switch from unit to
fused disconnect service. Repair as needed.
4. With ample voltage at line voltage connectors,
energize the furnace blower motor by jumpering
terminals R to G on the integrated ignition control.
5. With the blower motor in operation, the voltage
should be 115 volts ± 10 percent.
6. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the
local power company of the condition.
7. After completing check and/or repair, replace
Junction Box cover and reinstall the service panel
doors.
8. Turn on electrical power and verify proper unit
operation.
CHECKING WIRING
D
ALL
ISCONNECT
POWER BEFORE SERVICING.
1. Check wiring visually for signs of overheating, damaged
insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected
open wires.
3. If any wires must be replaced, replace with AWM,
105°C. 2/64 thick insulation of the same gauge or its
equivalent.
WARNING
M
ULTIPLE POWER
AILURE TO DO SO MAY CAUSE
WARNING
WARNING
CHECKING THERMOSTAT
D
ALL
ISCONNECT
POWER BEFORE SERVICING.
1. Remove the blower compartment door to gain access to
the thermostat low voltage wires located at the furnace
integrated control module terminals.
2. Remove the thermostat low voltage wires at the furnace
control panel terminal board.
3. Jumper terminals R to W (or W1 and W2 for two-stage
models) on the integrated ignition control.
With Power On (and Door Interlock Switch closed):
L
INE VOLTAGE NOW PRESENT
4. Induced Draft Motor must run and pull in pressure
switch.
5. If the hot surface ignitor heats and at the end of the
ignitor warm-up period the gas valve opens and the
burners ignite, the trouble is in the thermostat or
wiring.
6. With power off, check the continuity of the thermostat
and wiring. Repair or replace as necessary.
If checking the furnace in the air conditioning mode,
proceed as follows.
7. With power off, Jumper terminals R to Y
8. Turn on the power.
9. If the furnace blower motor starts and the
condensing unit runs, then the trouble is in the
thermostat or wiring. Repair or replace as necessary.
10. After completing check and/or repair of wiring and
check and/or replacement of thermostat, reinstall
blower compartment door.
11. Turn on electrical power and verify proper unit
operation.
CHECKING HEATING ANTICIPATOR
The heating anticipator on older thermostats is a wire
wound adjustable heater which is energized during the "ON"
cycle to help prevent overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail
for any reason, the thermostat must be replaced. Modern
thermostats do not have this type of heat anticipator. Many
have a selector switch to adjust the number of cycles per
hour.
WARNING
WARNING
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gcec80Amana amec80Amana acec80

Table of Contents