Slidewire Emulator Connections; Figure 3-13 Slidewire Connections - Honeywell HercuLine 10260A Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

3.4.7 Slidewire Emulator Connections

For connections, refer to Figure 3-11 and Figure 3-13.
ATTENTION
Shielded and grounded cables are recommended.
10
UP
11
DOWN
CONNECTION WHEN
AUTO/MAN SWITCH IS
NOT PRESENT
1
HOT
2
NEUTRAL
SLIDEWIRE
EMULATION
L
FB
H
36
35
34
SLIDEWIRE
SLIDEWIRE
SLIDEWIRE
SUPPLY
FEEDBACK
SUPPLY
COMMON
POSITIVE
2/03
10260A Series Actuators – Installation, Operations, and Maintenance
CW/CCW
SWITCH
12
CCW
CW
13
4 TO 20 mA INPUT
+
-
250 OHM
1%
30
RESISTOR
31
MOUNTED ON
TERMINAL
BOARD

Figure 3-13 Slidewire Connections

CONNECTION WHEN AUTO/MAN SWITCH
IS NOT PRESENT
AUTO
CCW
LIMIT
SW
CCW
C
NC
9
LL1
SW2
CW
AUTO/MAN SW
SW1
HL1
8
CCW
C
NC
CW
LIMIT
CW
SW
4 TO 20 mA OUTPUT
+
-
32
33
RESISTOR
MOUNTED AT INPUT
250 OHM
OF CUSTOMER'S
1%
INSTRUMENT
Installation
5
4
K
CCW
Motor
7
6
CW
G
AUTO/MAN
AUTO
SWITCH
CCW
CW
28
CLOSED WHEN
NOT IN AUTO
29
25

Hide quick links: