Inspection and maintenance
8.8

Setting the air/gas ratio

NOTICE
Setting the air/gas ratio
▶ The air/gas ratio is factory set and should not need to be adjusted. If
found to be out of tolerance and when all other possible causes have
been checked, please contact the Worcester Bosch Group helpline
0330 123 3366.
NOTICE
Combustion testing
▶ The checking of the air/gas ratio must be carried out by a competent
registered gas engineer, such as a Gas Safe registered engineer or
British Gas engineer.
▶ Checking of the air/gas ratio must not be attempted unless the
person carrying out the test is equipped with a flue gas analyser
conforming to BS7927 and is competent in its use.
All CO/CO
readings must be taken with the combustion chamber cover
2
ON.
Adjustments can only be made with the cover off.
CO
should be measured 10 minutes after firing the appliance.
2

Adjusting the minimum rated output settings

With the appliance in minimum rated output.
▶ Remove the seal from the adjusting screw of the gas valve (only gas
valve is shown in the below Figure 84) and set the CO
minimum rated output.
64
4mm
Fig. 84 Setting the CO
valves)
[1]
Gas valve - NG
[2]
Gas valve - LPG
▶ Re-check settings at maximum and minimum rated output and re-
adjust if required.
content for
2
▶ Seal the gas valve minimum adjustment.
▶ Exit the chimney sweep mode.
▶ Enter the CO

Adjusting the maximum rated output settings (LPG appliances)

With the appliance in maximum rated output.
▶ Insert the hex tool into the adjusting screw of the gas valve (as shown
in the below Figure 85) and set the CO
output.
Fig. 85 Setting the CO
▶ Re-check settings at minimum and maximum rated output and re-
adjust if required.
▶ Exit the chimney sweep mode.
▶ Enter the CO
MIN. %
1
MIN. %
T40
content (above: SIT valve, below: Honeywell
2
contents in the servicing record.
2
2
content
2
contents in the servicing record.
2
Greenstar 4000 – 6 720 891 162 (2020/09)
2
0010035321-001
content for maximum rated
MAX. %
4mm