Meaning of symbols on the display

Fault status message
Flame present
Valve controlled
Ignition controlled
Fan motor controlled
Oil preheater on
Heat request from controllers
Parameter setting mode
Info mode
Service mode
Actuator closing
Actuator opening
Unit of current display
Figure 18: Meaning of display
13.3

Special functions

13.3.1

Manual lockout

The reset must be carried out as follows:
Basic Documentation LME7...
13 Operation via AZL2
P
V
h min s
Press
together with any other button.
/reset
The basic unit switches instantly to the lockout
position, no matter what the operating position.
Display shows the fault status message.
(See chapter Error code list ...)
Display: Loc: 167
When the
/reset
rESEt appears on the display.
When the button is released, the basic unit is
reset.
%
button is pressed for 1 second,
CC1P7105en
17.04.2018
55/106