Trouble Analysis; General - Trane CLCP Euro 25 Installation Operation & Maintenance

Quantum climate changer air handlers
Table of Contents

Advertisement

Trouble Analysis

General

Use the tables in this section to assist in identifying the cause or causes of a malfunction in Air Handler operation. The column
header RECOMMENDED ACTION will suggest repair procedures.
Note: These tables are intended as a diagnostic aid only. For detailed repair procedures, contact your local Trane Service
Company.
Symptom
Bearing noise
Bearing is excessively hot
Motor stalls
Motor overheats
Excessive vibration
Excessive vibrator
Excessive motor noise
Excessive fan noise
Premature belt wear
Filter collapsing
Probable Cause
Poor alignment
Inadequate lubrication
Overtensioned belts
No lubricant (plummer block type)
Overlubrication
Misaligned bearing
Low line voltage
Short circuit, phase to earth (open Phase)
Overloaded motor
Motor fan is clogged with dirt preventing
proper ventilation
Overloaded motor
Motor fan damaged
Poor pulley alignment
Transport brackets not removed
Overtensioned belts
Fan / unit vibration isolator collapsed
Misalign drive
Motor mounting bolts loose
Worn motor bearings
Fan rubbing on fan cover
Fan rubbing on inlet cone or guard
Worm fan bearings
Loose impeller
Incorrect tension or alignment
Dirt or grease on belts
Belts rubbing
Odd belts being fitted
Blocked with dirt
Air velocity too high
Filter wrong size
Loosen bearing setscrews and realign
Grease bearing(s) (Plummer block)
Retension belts
Apply grease
Clean surface of grease and purge
Correct alignment and check that shaft is level
Check across AC line. Correct voltage if possible
Check line phases and terminal block connection.
Reduce system load, fan driven speed or increase
motor capacity
Remove fan cover, clean fan and replace cover
Reduce load or replace with larger motor
Replace motor fan / clean
Check pulley alignment
Remove items used for transport only
Retension belts
Replace vibration isolator
Align drive
Tighten motor mounting bolts
Replace bearings and seals
Remove interference in motor fan housing
Remove item and repair
Replace bearings and seals
Retighten hub
Re-tension and align
Clean belts and pulleys; check for grease leaks
Remove obstruction
Replace with full set
Change at advised dirty condition
Check unit running conditions Replace
with filter sizes as supplied from Trane
41
Recommended Action

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Clcp euro 50Clcp euro xp

Table of Contents