The following diagram illustrates the normal sequence of connection configuration
triggered by an IP_CONFIG in the user program.
The job executes as soon as the parameter ACT is transferred with value 1.
Due to the segmented transfer of the CONF_DB, you will need to repeat the job
with ACT = 1 until completion of the job is indicated in the parameters
ERROR, and STATUS.
If you want to transfer a connection configuration again later, the parameter ACT
must first be transferred with value 0 in at least one further call.
User program
(CPU cycle)
Supply CONF_DB with
CONF_DB is
transferred in
segments.
Legend:
1)
Parameter transfer DONE, ERROR, STATUS
Notice
The data transferred with the configuration DB are stored in volatile memory on
the CP and must be downloaded to the CP again following a power down!
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FB55 IP_CONFIG - continued
data
Set ACT = 1
Call IP_CONFIG
0, 0, Job active
Call IP_CONFIG
0, 0, Job active
Call IP_CONFIG
Job completed without error
Set ACT = 0
Call IP_CONFIG
Time
Ethernet CP
1)
S
CP is supplied with system data
(including the IP address);
S
Connections are configured on the
CP.
1)
1)
Time
DONE,
A -227