Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 121

Digital boiler control unit
Table of Contents

Advertisement

Coding 2
(continued)
Overview of all codings (continued)
Coding as per
Function
factory setting
Address: Value
2C: 5
2C: 5
Maximum run-on time of boiler isolation
Maximum run-on time of boiler isolation
General
General
valve 5 minutes
valve 5 minutes
2d: 0
Shunt pump ON only when requested
Boiler
40:125
Operating time of actuating drive, boiler
General
isolation valve, 3-port mixing valve or
mixing valve motor in conjunction with
return temperature raising facility
125 seconds
Plug aJA not installed
4A: 0
General
Plug aJB not installed
4b: 0
General
Connections at plug sÖ A1:
Connections at plug sÖ A1:
4C: 2
4C: 2
General
General
Therm-Control switch contact
Therm-Control switch contact
Connections at plug sL:
Connections at plug sL:
4d: 1
4d: 1
General
General
Shunt pump
Shunt pump
Connections at plug gS:
4E: 0
General
Boiler isolation valve or 3-port mixing
valve for return temperature raising facility
4F: 5
4F: 5
Shunt pump, boiler circuit pump or
Shunt pump, boiler circuit pump or
General
General
distributor pump with 5 minutes run-on
distributor pump with 5 minutes run-on
time
54: 0
Without solar control unit
General
Additional information
New coding
Possible change
Address:
Value
2C: 0
No run-on time
2C: 1
Run-on time adjustable
to
from 1 to 60 minutes
2C: 60
2d: 1
Shunt pump ON continuously
40: 5
Operating time adjustable
to
from 5 to 199 seconds
40:199
Plug aJA installed
4A: 1
(e.g. temperature sensor of
Therm-Control);
automatically recognized
Plug aJB installed
4b: 1
(e.g. temperature sensor T2);
automatically recognized
4C: 1
Primary pump of DHW heating
4C: 3
Circulation pump of flue gas/water
heat exchanger
4d: 2
Boiler circuit pump
4d: 3
Boiler circuit pump with boiler
isolation valve function
4E: 1
3-port valve of DHW heating
4F: 0
No pump run-on
4F: 1
Run-on time adjustable
to
from 1 to 60 minutes
4F: 60
54: 1
With Vitosolic 100;
will be recognised automatically
54: 2
With Vitosolic 200;
will be recognised automatically
121

Advertisement

Table of Contents
loading