Coding 1 - Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Additional information

Coding 1

(continued)
Codings (continued)
Coding as per
Function
factory setting
Address: Value
07: 1
Boiler
*1
08:
Burner
(mod.)
*1
09:
Burner
(mod.)
*1
0A:
Burner
(mod.)
*2
15: 10
Burner
(mod.)
40:125
General
77: 1
General
*1
The factory setting is determined by the boiler coding card.
*2
This setting is matched to the Vitocrossal.
116
Boiler sequence number in multi-
boiler system (in conjunction with
coding address "01")
Max. output of burner in kW
Max. output of burner in kW
Basic output of burner in %
Operating time of actuating drive
Operating time of actuating drive,
boiler isolation valve, 3-port mixing
valve or mixing valve motor in
conjunction with return
temperature control 125 minutes
LON participant number
New coding
Possible change
Address:Value
07: 2
Boiler sequence number in multi-boiler
to
system (in conjunction with coding
07: 4
address "01")
08: 0
Maximum output variable from
to
0 to 99 kW;
08: 99
1 increment = 1 kW
09: 0
Maximum output variable from
bis
0 to 19900 kW:
09:199
1 increment = 100 kW
0A: 0
Basic output in kW
to
Max. output in kW
0A:100
Basic output in %
15: 5
Operating time variable
to
from 5 to 199 seconds
15:199
40: 5
Operating time adjustable
to
from 5 to 199
40:199
77: 2
LON participant number
to
selectable from 1 to 99
77: 99
Please note:
Each number may be assigned once only.
x100% =