Place the valve spring inside the valve body and secure it with the valve cover and two opposing bolts. Ensure
that the valve seat plug is not tilted.
Uniformly tighten the nuts of the two bolts to raise the valve cover and compress the spring.
With the valve cover in position against the valve body, insert two of the mounting screws into the available
cover holes.
Remove the two bolts and replace them with the other two mounting screws. Ensure that the valve body and
cover are sealed.
Open the upstream shutoff cock and check for leakage along the valve cover. (Refer to the Checkout
Procedure section).
Observe at least three complete operating cycles to ensure that all components are functioning correctly.
Valve Model
Rp ¾ - 1½ und DN 40
Rp 2- 3 und DN 50 - 80
DN100 -150
Table 3: Torques
Strainer,
filter
Flanged bodies DN40-80 and all
threaded valve bodies
Figure 4: Detailed drawing
Johnson Controls SA/NV - Leuvensesteenweg 248D - B-1800 Vilvoorde - +32(2) 709 40 00 - www.johnsoncontrols.be
Page:13
Locking screw
Valve Cover
10 Nm
25 Nm
25 Nm
Distance piece
Valve
seat
plug
Valve
spring(s)
Valve cover
Cover mounting
screws
Flanged ring actuator
-
-
8 Nm
Flanged valve bodies DN100-150
130 4280 010 E
5 Nm
5 Nm
5 Nm
Grub screw
Locking
screw