Default Settings; Basic Setup And Programming For Offline Access Control - Interlogix ATS1170 Programming Manual

One door ras
Table of Contents

Advertisement

ATS format cards will show codes similar to:
00, 43, 46, 00, 00 91
#-Exit
Financial Institution cards will show codes similar to:
52, 16, 29, 52, 60, 1E
#-Exit
ATS 1170 menu 11–Number of Cards in database
Select menu 11–Number of Cards and press Enter to view the number of cards
already held in ATS1170 database. The display will show information similar to:
Number of Cards 15
#-Exit
15 being the number of cards already programmed into the database.
Returning to the control panel installer menu
To return to the control panel installer menu, press 0 (zero) followed by Enter at
the main menu.

Default settings

Database: Empty
Unlock Time: 5 seconds
Request to Exit: Request to Exit Only
Card format: Dipswitch C Setting
Card type: Dipswitch B Setting
LED 1: Door Unlocked + disarmed
LED 2: Armed

Basic setup and programming for offline access control

Should the control panel ever fail or the communication fail between the control
panel and ATS1170, the ATS1170 module has the capacity to continue operating
as a standalone unit with its own power supply. In this offline mode, cards
programmed into the ATS1170 onboard database will be used to determine
access control, while those cards stored in the control panel database cannot be
used. Bearing this in mind it is important to take due consideration when
selecting those cards which will make up the 15 cards in the off-line onboard
database. They will be the only users who have access when the control panel
user database is no longer accessible. During this time the integrity of the
security system is under suspicion.