Installing the PRO4200 Two Reader Module
Wiring Diagram for Connectors TB1,TB7-9
(within 12 inches [30cm]); the effectiveness of the circuit decreases as the distance
from the load increases.
Only relays 0 and 2 can be used for door hardware in a UL installation
Note:
Relays 1 and 3 are dry-circuit level signal relays typically used to indicate the status of
the door lock. Relays 4 and 5 are general-purpose relay outputs and are not available
when the board is rack-mounted.
Use sufficiently large gauge of wires for the load current to avoid voltage loss.
Mounting Options
This board can be mounted on-edge in the rack-mount enclosure provided by
Honeywell or it can be mounted flat against any surface using standoffs under the
mounting holes provided in each of the four corners of this board.
When this board is rack-mounted, the connectors for two general-purpose inputs, two
general-purpose outputs, and two dedicated inputs are not accessible and should not
be used.
The most common reason for mounting a board flat is that it is being installed
remotely to be located near the door(s) being monitored. In this case it will be
mounted in its own enclosure creating the need to monitor cabinet tamper and power
fault detection inputs. The two additional general-purpose inputs and outputs provided
allow for the monitoring of extra sensors and control of local horns or other
equipment.
Installing the Module
1. Set Jumpers and DIP switches.
2. Mount this board in the appropriate enclosure - If this board is being mounted
3. Connect the communications and power supply to the circuit boards with the
Warning:
UNTIL ALL WIRING HAS BEEN INSTALLED AND RECHECKED.
4. Connect wiring to the reader interfaces as appropriate.
5. Connect wiring to input sensors or install jumper wire as appropriate.
22
in a rack, the component side of the board is to your right as you face the rack.
Power Supply Harness.
DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET
www.honeywell.com