Pre-Installation Checklist; Burner - Eclipse TA Series Installation Manual

Thermair burners
Table of Contents

Advertisement

p
-
re
iNstallatioN
C
heCklist
b
urNer
Minimum 1/4" (6mm)
space per side
Combustor
Chamber wall
"C"
Air Supply
Provide an opening in the burner room of at least one square
inch per 4000 BTU/hr (6 cm
intake with fresh, outdoor, combustion air.
If there are corrosive fumes or materials in the surrounding air,
find an uncontaminated source to supply air to the burner.
Exhaust
Do not allow exhaust gases to accumulate in the work area.
Provide a means for exhausting these gases from the building.
Access
Install the burner so it may be easily accessed for inspection and
maintenance.
Environment
Be sure the burner operating environment matches the original
operating specifications. Check the following items:
voltage, frequency, and stability of electrical power
fuel type and fuel supply pressure
adequate fresh, clean, combustion air
humidity, altitude, and temperature of the supply air
presence of damaging corrosive gases in the air
prevent direct exposure to water.
Chamber Opening
Provide an opening in the chamber wall at least ½" (12mm)
larger in diameter than the outside diameter of the combustor.
Provide an accessible pressure tap on the chamber wall to
measure the pressure inside the firing chamber. The pressure
tap should be located near the burner.
Mounting Pattern
Attach four mounting bolts to the chamber wall. Position these
bolts to match the clearance holes (C) on the burner mounting
flange. Refer to the appropriate ThermAir data sheet.
Eclipse ThermAir T/A Series v1.10, Installation Guide No. 114, 4/7/06
per 1 kW) to supply the burner
2
1