Ground Wiring - Emerson EVH Series Installation Manual

Variable frequency drive
Table of Contents

Advertisement

Ground Wiring

Warning!
Connect only in a voltage-free state!
Note:
Do not wire motor leads to R+, R–. This will cause damage to the drive.
➀ Actual layout may vary slightly by frame.
Note:
Ground Wiring
Run motor cables in separate conduit
DO NOT RUN CONTROL WIRES in same conduit
Cables sized per below tables for Cables & Fuses
Provide dedicated wire for low impedance ground between drive and motor. DO NOT USE conduit as ground
Improper grounding could result in damage to the motor and/or drive and could void warranty.
17