Wire Stripping Lengths - Emerson EVH Series Installation Manual

Variable frequency drive
Table of Contents

Advertisement

Input Power and Motor Cable Stripping Lengths
Size
FR1
FR2
FR3
FR4
FR5
FR6
Power Wiring in Inches (mm)
A1
B1
C1
0.39
1.77
0.39
(10)
(45)
(10)
0.59
1.77
0.59
(15)
(45)
(15)
0.59
1.57
0.59
(15)
(40)
(15)
0.98
2.56
0.98
(25)
(65)
(25)
1.10
6.10
1.10
(28)
(155)
(28)
0.98
4.72
0.98
(25)
(120)
(25)
Power Connection Tightening Torque
Frame
Power wire
Size
in-lb (Nm)
FR1
5.3 (0.6)
FR2
15.6 (1.8)
FR3
40 (4.5)
FR4
95 (10.7)
FR5
354 (40.0)
FR6
480 (54.2)
Notes:
-
Strip the motor and power cables as shown above.
-
Both UL and IEC tools may be used
-
Applies to strained wire, solid wire, or ferrule installations
Motor Wiring in Inches(mm)
D1
A2
B2
1.38
0.39
1.77
(35)
(10)
(45)
1.77
0.59
1.57
(45)
(15)
(40)
1.97
0.59
1.57
(50)
(15)
(40)
4.72
0.98
2.56
(120)
(25)
(65)
9.45
1.10
6.10
(240)
(28)
(155)
7.87
0.98
4.72
(200)
(25)
(120)
Ground
Control wire
wire
in-lb (Nm) @
in-lb (Nm)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
14 (1.6)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
C2
D2
0.39
1.38
(10)
(35)
0.59
1.57
(15)
(40)
0.59
1.97
(15)
(50)
0.98
4.72
(25)
(120)
1.10
9.45
(28)
(240)
0.98
7.87
(25)
(200)
15

Advertisement

Table of Contents
loading

Table of Contents