Event Input Function; Event Input Npn/Pnp Input Mode Setting; Event Input N-O/N-C Input Mode Setting - Omron KM1 User Manual

Smart power monitor
Table of Contents

Advertisement

0BChapter 3
Functions
3.4
3.4

Event input function

Event input function

Number of input points: 7
Number of input points: 7
Counts pulses by judging a pulse output from external equipment as an input.
Counts pulses by judging a pulse output from external equipment as an input.
Calculates power original unit by dividing integrated power amount by pulse input count.
Calculates power original unit by dividing integrated power amount by pulse input count.
Measures pulse input ON time.
Measures pulse input ON time.
Classifies energies according to event input conditions. (3-STATE function)
Classifies energies according to event input conditions. (3-STATE function)
* Power original unit is used for measuring tact power of product lines. Pulse input ON time
* Power original unit is used for measuring tact power of product lines. Pulse input ON time
is used for calculating operation time of equipment.
is used for calculating operation time of equipment.

Event input NPN/PNP input mode setting

Event input NPN/PNP input mode setting

PMU1A
PMU1A
PMU2A
PMU2A
(Electric
(Electric
(Power
(Power
power)
power)
two-system)
two-system)
×
×
Performs switching between input without voltage and with voltage in event inputs 1 to 7.
When using this function for relays, etc., take into account chattering, etc. that will occur.
On resistance: 1 kΩ or less, Off resistance: 100 kΩ or more
With Voltage (PNP) means an input for switching ON/OFF by applying voltage to the event
input terminal.
H level: 4.75 to 30 VDC, L level: 0 to 2 VDC
Setting range: PNP, NPN (Initial value: PNP)

Event input N-O/N-C input mode setting

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
×
×
Performs switching between Normally open and Normally closed in the event input.
Normally open (N-O) judges an open (release) state as event OFF, and a closed
(continuity) state as event ON.
On the other hand, Normally closed (N-C) judges a closed (continuity) state as event ON,
and an open (release) state as event OFF.
Setting range
The time chart of Normally open is as follows.
Event input
イベント入力
Judgment
The time chart of Normally closed is as follows.
Event input
イベント入力
Judgment
判定
3-16
EMU8A
EMU8A
CTD8E
CTD8E
(Pulse/temperature)
(Pulse/temperature)
(CT
(CT
expansion)
expansion)
×
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
N-O, N-C
:
OFF
ON
OFF
ON
OFF
ON
O: With setting X: Without setting
O: With setting X: Without setting
(Initial value: N-O)
ON
OFF
OFF
ON

Advertisement

Table of Contents
loading

Table of Contents