Installation; Unit Location - Basic Requirements; Unit Location - Position Selection; Clearance - Panasonic PAW-FC Installation And Maintenance Manual

Fan coils
Hide thumbs Also See for PAW-FC:
Table of Contents

Advertisement

5.

Installation

CAUTION
-
The unit installation work must be done by qualified personnel according to the local rules and this manual.
-
The unit should not be installed in a bathroom, a laundry, a sauna or a swimming-pool.
During the installation:
Take care to avoid any rough handling or impacts when
unloading and moving the appliance.
Before hoisting into position, test lift to insure stability and
balance. Avoid twisting or uneven lifting of the units.
The units shall be carefully inspected before unit
installation to make sure that no handling damage has
occurred.
5.1 Unit location – basic requirements
Installation in the following places may cause malfunction. If it is unavoidable, please contact the technical centre.
Place where strong heat sources, vapours, flammable gas
or volatile objects are emitted.
Place where high-frequency waves are generated by radio
equipment, welders and medical equipment.
Place where a lot of salinities such as seaside exists.
Place where the oil (machine oil) is contained in the air.
5.2 Unit location – position selection
The air inlet and outlet vent should be far from any
obstruction, make sure that the air can be blown through
the whole room.
Select a position where the condensing water can be
drained easily.
Select a location where children cannot reach the unit.
Select a place strong enough to withstand the full weight
and vibration of the unit (will not increase the noise).
Be sure to leave enough space to allow access for
maintenance. The height of the installed location should
be 200 cmor more from the floor.

5.3 Clearance

The figure on the right shows the minimum distances
recommended for the correct operation of the unit:
1.
2.
3.
4.
5.
Space to the ceiling
Space to the wall
Air outlet side
Space to the floor
Space to the wall
All these sections have been inspected before leaving the
factory. It is therefore important to insure that no bolts,
screws or other fixing system are loosened or missing
before the commissioning. During the handling of the
machine it is mandatory to provide all the devices
necessary to guarantee personal safety.
Place where a sulphured gas such as the hot spring
zones is generated.
Other place with special application.
Select a place about 1m or more away from TV set or
any other electric appliances.
Select a place where the filter can be easily taken out.
Make sure that the unit installation is according to
installation dimension diagram requirements.
Do not use the unit in the immediate surroundings of a
laundry, bath, shower or swimming pool.
1
15
cm
2
15 cm
3
250
cm
9
5
15 cm
200
cm
4