Indoor Unit Installation
Ceiling board
Fig. 2.
MODEL
Length of A (mm)
18
205
24
205
30
205
30-48
245
48-60
287
Table 3. Distance from ceiling relative to height of indoor unit
Step 2: Hang indoor unit.
1. Use the included paper template to cut a rectangular hole in the
ceiling, leaving at least 1 m on all sides. The cut hole size should be
40 mm larger than the body size (See Fig. 3).
Ensure to mark the areas where ceiling hook holes will be drilled.
Refrigerant piping side
780 mm (Suspension bolt)
840 mm (Body)
950 mm (Ceiling opening)
18-48K ceiling hole size
Fig. 3.
8
Connecting point of
drain pipe
>2.5 m
Length of H (mm)
> 235
> 235
> 235
> 275
> 317
Drain hose side
Ceiling
880 mm (Ceiling hole)
Ground
Refrigerant piping side
840 mm (Suspension bolt)
900 mm (Body)
1020 mm (Ceiling opening)
Fig. 4.
Connecting point of refrigerant
pipe (liquid side)
Connecting point of refrigerant
pipe (gas side)
Front panel
Drain hose side
60K ceiling hole size