Summary of Contents for Bosch Climate 5000 RAC 2,6-2 OU
Page 1
Installation Manual SPLIT-TYPE ROOM AIR CONDITIONER Climate 5000 RAC 2,6-2 IBW / OU- OUE RAC 3,5-2 IBW / OU- OUE RAC 5,3-2 IBW / OU- OUE RAC 7-2 IBW / OU- OUE IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
Safety Precautions Table of Content Safety Precautions Read Safety Precautions Before Installation Safety Precautions ............2 Incorrect installation due to ignoring instructions can cause serious Accessories ............... 4 damage or injury. Installation Summary - Indoor Unit ........6 The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
Page 3
Safety Precautions Note on Fluorinated Gasses 7. The appliance should not be installed in a room with a continuous heat source (for example: open flames, an operating gas appliance 1. This air-conditioning unit contains fluorinated gasses. For specific or an operating electric heater) information on the type of gas and the amount, please refer to 8.
Accessories Accessories The air conditioning system comes with the following accessories. Use Improper installation may result in water leakage, electrical shock and all of the installation parts and accessories to install the air conditioner. fire or cause the equipment to fail. Name Shape Quantity...
Page 5
Accessories Name Shape Quantity Remote controller illustration AIR CONDI TIONE R REMOTE CONTROL LER I LLUSTRATI ON Connecting pipe assembly Liquid side Ø6. 35 Parts you must purchase Ø9. 52 Gas side Ø9. 52 Ø12. 7 Ø16 Ø19 Table 1. WARNING Appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
Unit Parts Unit Parts NOTE: The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas. Power isolator (1) (2) Fig. 1. 1. Wall Mounting Plate 2. Front Panel 3.
Indoor Unit Installation Indoor Unit Installation Refer to the following diagram to ensure proper distance from walls and ceiling: 15cm or more 12cm 12cm or more or more Fig. 2. 2.3m or more Installation Instructions – Indoor Unit Fig. 3. Prior to installation Before installing the indoor unit, refer to the label on the product box Step 2: Attach mounting plate to wall...
Indoor Unit Installation 3. Use scissors to cut down the length of the insulating sleeve to reveal Step 5: Connect drain hose about 15cm of the refrigerant piping. This serves two purposes: By default, the drain hose is attached to the left- hand side of unit (when you’re facing the back of the unit).
Indoor Unit Installation WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, ISOLATE MAIN POWER TO THE SYSTEM. INCORRECT Kinks in the drain hose Step 6: Connect signal cable will create water traps. The signal cable enables communication between the indoor and outdoor units.
Indoor Unit Installation 2. Open front panel of the indoor unit. Step 7: Wrap piping and cables Before passing the piping, drain hose and signal cable through the wall 3. Using a screwdriver, open the wire box cover on the right side of the hole, you must bundle them together to save space, protect them and unit.
Outdoor Unit Installation If refrigerant piping is already embedded in the wall, do the following: Outdoor Unit Installation 1. Hook the top of the indoor unit on the upper hook of the mounting plate. 2. Use a bracket or wedge to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable and drain hose.
Outdoor Unit Installation Special considerations for extreme weather If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds.
Outdoor Unit Installation 8. Bolt the unit firmly to the brackets. Outdoor unit dimension Mounting dimensions mm (WxHxD) To reduce vibrations of wall- mounted unit Distance A Distance B (mm) (mm) If allowed, you can install the wall-mounted unit with rubber gaskets to reduce vibrations and noise.
Page 17
Outdoor Unit Installation 1. Prepare the cable for connection: USE THE CORRECT CABLE • Indoor Power Cable (if applicable): H05VV-F or H05V2V2-F • Outdoor Power Cable: H07RN-F • Signal Cable: H07RN-F Cover Minimum Cross-Sectional Area of Power and Signal Cables •...
Refrigerant Piping Connection Refrigerant Piping Connection WARNING DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage, dent or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit. 1.14.2 Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping connection.
Refrigerant Piping Connection Radius ≥10cm Fig. 31. Fig. 33. Piping extension beyond flare form Instructions for Connecting Piping to Indoor Unit Outer Diameter of pipe A (mm) 1. Align the centre of the two pipes that you will connect. See Fig. 34. (mm) Min.
Page 20
Refrigerant Piping Connection WARNING DO NOT USE EXCESSIVE TORQUE Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements shown in the table. Instructions for Connecting Piping to Outdoor Unit 1. Unscrew the cover from the packed valve on the side of the outdoor unit.
Air Evacuation Air Evacuation 5. Run the vacuum for at least 15 minutes or until the Compound Meter reads -76cmHG (-10 Pa). 6. Close the Low Pressure side of the manifold gauge and turn off the vacuum pump. 7. Wait for 5 minutes, then check that there has been no change in system pressure.
Page 22
Air Evacuation ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length Air Purging Additional Refrigerant Method ≤ Standard Pipe Length Vacuum Pump > Standard Pipe Length Vacuum Pump Liquid Side: Ø 6.35 Liquid Side: Ø 9.52 R32: R32: (Pipe length – standard length) x 12g/m (Pipe length –...
Electrical and Gas Leak Checks Electrical and Gas Leak Checks Test Run Before Test Run Only perform test run after you have completed the following steps: • Electrical Safety Checks – Confirm that the unit’s electrical system is safe and operating properly •...
European Disposal Guidelines IF AMBIENT TEMPERATURE IS BELOW 17°C (63°F) European Disposal Guidelines This appliance contains refrigerant and other potentially hazardous You cannot use the remote controller to turn on the COOL function when materials. When disposing of this appliance, the law requires special the ambient temperature is below 17°C.
Information Servicing Information Servicing • marking and signs that are illegible should be corrected; • refrigeration pipe or components are installed in a position where (Required for the units adopt R32 Refrigerant only) they are unlikely to be exposed to any substance which may corrode 1.
Page 26
Information Servicing 13. Detection of flammable refrigerants • Prior to recharging the system it must be pressure tested with OFN. The system must be leak tested on completion of charging but prior Under no circumstances should potential sources of ignition be used to commissioning.
Page 27
Information Servicing • The recovery equipment should be in good working order with a set of instructions concerning the equipment that is at hand and should be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales should be available and in good working order.
Page 28
Bosch Thermotechnology Ltd Cotswold Way Warndon Worcester WR4 9SW mailto: Commercial.enquiry@uk.bosch.com Contact Number 03301233004 Web address www.bosch-industrial.co.uk...