34
en | Mounting

Parts included

1 smoke alarm device: base (3.A) and detector head (3.B), 2 batteries,
fastening material: 1 screw, 1 plug
2
Mounting
Notice!
The device is designed for mounting according to DIN 14676
on flat or slanted ceiling. Wall mounting is not allowed.
Perform the following steps. Find exact information about the single
steps on the following pages in this manual. See also the graphics at
the beginning of this manual.
1. Determination of mounting locations. (1) Observe the information
regarding Unsuitable locations for mounting, page 34, and regarding
Audibility, page 35. Each device is to be mounted horizontally on
the ceiling in centered position with a minimum distance of 0.5m to
walls and objects. On slanted ceilings >20° it is to be mounted 0.5m
to 1m from the top of the ceiling. (2.A), (2.B), (2.C), (2.D)
2. For each device: Inserting batteries, page 35. Observe the polarity.
(6.1)
3. For each device: Mounting the base. (5) Observe the marks (5.1) for
alignment with BOSCH label/siren.
4. Functional check, page 35, for each device after setting it up into
operation. (6) (7)
Unsuitable locations for mounting
Kitchen/bathroom (steam)
Rooms with open fireplaces (fumes)
In the immediate vicinity of halogen lamps, transformers,
fluorescent or energy-saving lamps
08.2015 | 3.1 | F.01U.309.848
Bosch Sicherheitssysteme GmbH
Smoke Alarm