12.7 Vertical Airflow Direction Control

12.7.1
Auto Control
(Cooling and Soft Dry Operation Condition)
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.
For CS-A9MKD and CS-A12MKD
For CS-A18MKD, CS-A24MKD and CS-A28MKD
(Heating Operation Condition)
When the piping air temperature reaches 38°C, the louver is changed from upper to lower limit. When the piping
air temperature falls 35°C, the louver is changed from lower to upper limit.
For CS-A9MKD and CS-A12MKD
Closing
22°
position
Swing up and down
/ 135°
Lower limit for cooling mode and
soft dry mode/33°
Closing
position
22°
/ 148°
Lower limit for cooling mode and
soft dry mode/39°
Closing
position
51°
/ 135°
Lower limit for heating mode/62°
60
Horizontal
Upper limit for cooling mode
and soft dry mode/11°
Horizontal
Upper limit for cooling mode
and soft dry mode/17°
Swing up and down
Horizontal
Upper limit/11°