3.3 Interface description
3.3.7

X42 terminal strip

Table 3- 5
Connector
Max. connectable cross-section: 2.5 mm
Note
Connection options for terminal strip X42
The terminal strip is not intended to be freely used for other 24 V DC loads (for example for
supplying additional line-side components), as the voltage supply of the Control Interface
Module could also be overloaded and operating capability could thus be compromised.
3.3.8

X46 Brake control and monitoring

Table 3- 6
Connector
Max. connectable cross-section: 1.5 mm
Note
The interface is intended for connection of the Safe Brake Adapter.
Fire due to overheating when the total length of the connecting cables is exceeded
Excessively long connection cables on terminal strip X46 can cause components to overheat
with the associated risk of fire and smoke.
• Limit the length of the connecting cables to a maximum of 10 m.
• Do not route the connection cable outside the control cabinet or control cabinet group.
30
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
Function
1
P24L
2
3
M
4
Terminal strip X46 brake control and monitoring
Terminal
Function
1
BR output +
2
BR output -
3
FB input +
4
FB input -
WARNING
Air-Cooled Chassis Power Units - supplement to Motor Module 6SL3320-1TG41-5AA3
Technical specifications
Power supply for Control Unit, Sensor Module and
Terminal Module (18 ... 28.8 V)
maximum load current: 3 A
2
Technical specifications
Brake connection
Supply voltage: 24 V DC
Max. load current: 200 mA
Internal feedback signal from the Safe Brake
Adapter
2
Equipment Manual, 10/2020, A5E50422764A