Environmental and Safety

Table 31. Electrical Output Specifications (Continued)
Isolation, Including Output
Neutral to Ground Bonding
Load Compatibility
Overload Capability
Output Voltage THD
Short Circuit Protection
Transfer Time To Battery
Efficiency
1 1 2 2 . . 2 2 E E n n v v i i r r o o n n m m e e n n t t a a l l a a n n d d S S a a f f e e t t y y
Table 32. Environmental and Safety Specification
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Ventilation
Lightning and Surge Protection
Audible Noise (dB)
Heat Dissipation
74
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User's Guide P-164000906—Rev 05
The Eaton Ferrups FX UPS provides a true, separately-derived power source, as defined by
National Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct
connection between input and output, and less than 2 pF of effective input to output
capacitance.
UPS supports R, RCD, SMPS, and PFC loads
RCD Loads shall have a minimum power factor of 0.7
Supports Load Crest Factor up to 2.5
On line with 101 - 124% load, shutdown in 10 minutes
On inverter with 101 - 110% load, shutdown in 10 minutes
On line with more than 125% load, shutdown in 10 seconds
On inverter with more than 110% load, shutdown in 10 seconds
<10% at full resistive load, under normal operating conditions and with the batteries fully
charged with the charger in the rest mode.
Shutdown after 3 line cycles of output short circuit that cannot be cleared.
Transfer to Battery Mode operation from Normal Mode operation in zero milliseconds
The UPS efficiency with Line-to-Line Load shall be > 80% with charger off
The UPS efficiency with Line-to-Neutral Load shall be > 88% with charger off
0°C to 40°C (32°F to 104°F)
UPS with batteries: –15° to 40°C (4° to 104°F)
UPS without batteries: —40° to 60°C (-40° to 140°F)
0–95% noncondensing
The maximum operating ambient temperature decreases 1° C per 300 m above sea level
(2° F per 1000 ft above sea level). Maximum elevation is 10000 m (32,808 ft )
The air around the UPS must be clean and free of dust, corrosive chemicals, and other
contaminants. The Eaton Ferrups FX UPS uses internal fans to circulate the air for cooling.
The air must be free to circulate around the UPS and external battery cabinet(s). Do not
operate the UPS in a sealed room or container.
The Eaton Ferrups FX UPS provides 2000-to-1 spike attenuation. Tested using lightning
standard per ANSI/IEEE C62.41 Category A (6000V spike and 200A) and Category B
(6000V spike and 3000A) test, and ANSI/IEEE C62.45 test procedures.
Online
65
BTU / Hour (On line with Full Load)
905
Battery
62